💧 Free CHW Pipe Sizer

Chilled Water Pipe Sizing Calculator

Size chilled water, condenser water and heating hot water pipes from cooling load (TR or kW) or directly from flow rate. Uses the ASHRAE rule — 4 ft/s below 2″, and 4 ft per 100 ft with an 8 ft/s cap above 2″. Schedule 40 steel and Type L copper, US and metric.

💧 CHW Pipe Size Calculator

Sets design temperature, default ΔT and velocity limits
Size from
TR
°F
= 2.40 GPM per TR
ft
Straight pipe + equivalent length of fittings and valves — gives total head for pump selection
Design limits & water temperature
ft/s
ft/s
ft/100ft
°F

Temperature sets viscosity and density. Chilled water at 45 °F is about four times more viscous than hot water at 180 °F, which changes friction loss noticeably. Roughness is 0.045 mm for steel and 0.0015 mm for copper.

📊 Chilled Water Pipe Size Chart — TR & GPM to Pipe Size

Schedule 40 steel, chilled water at 49 °F mean, sized with a 4 ft/s velocity limit at 2″ and below and a 4 ft per 100 ft friction limit with an 8 ft/s cap above 2″. Tonnage is converted at a 10 °F ΔT, which gives 2.4 GPM per TR. Values come from the same engine as the calculator above.

Load (TR)Flow (GPM)Flow (L/s)Pipe sizeDNVelocity (ft/s)Velocity (m/s)Friction (ft/100ft)Friction (Pa/m)
120.21/2"DN152.530.776.96208
250.33/4"DN202.890.886.12183
370.51"DN252.670.813.89116
5120.81-1/4"DN322.570.782.5676
7.5181.11-1/4"DN323.861.185.38161
10241.51-1/2"DN403.781.154.27127
15362.32"DN503.441.052.6278
20483.02-1/2"DN653.220.981.8555
25603.82-1/2"DN654.021.232.7983
30724.52-1/2"DN654.821.473.92117
40966.13"DN804.171.272.2868
501207.63"DN805.211.593.46103
7518011.44"DN1004.541.381.9157
10024015.14"DN1006.051.843.2898
15036022.75"DN1255.771.762.2768
20048030.35"DN1257.702.353.92117
30072045.46"DN1508.002.443.37101
40096060.68"DN2006.161.881.4744
5001,20075.78"DN2007.702.352.2567
7501,800113.610"DN2507.322.231.5546
1,0002,400151.412"DN3006.882.101.1233
1,5003,600227.116"DN4006.541.990.7723
2,0004,800302.818"DN4506.882.100.7422
3,0007,200454.224"DN6005.751.750.3711

For condenser water at 3 GPM per TR, read the chart at 1.25 times your tonnage. For copper Type L the internal diameter is smaller than steel at the same nominal size, so a copper line often lands one size larger — use the calculator with copper selected rather than this chart.

ℹ️ How to Use This CHW Pipe Sizing Calculator

  1. Pick the fluid. Chilled water, condenser water or heating hot water. This sets the design temperature, the default ΔT and the velocity limits — condenser water is normally allowed a little more velocity in plant rooms.
  2. Pick the material. Schedule 40 black steel is standard for mains; Type L copper is common on small branches and has a smaller bore at the same nominal size.
  3. Enter tonnage or flow. If you work from equipment schedules in TR or kW, use the load option and the tool converts with GPM = TR × 24 ÷ ΔT. If you already have a flow rate from a coil schedule, switch to flow.
  4. Enter the pipe run length including the equivalent length of elbows, valves, strainers and balancing devices. The tool returns total head loss, which is the piping contribution to pump head.
  5. Check the two candidate sizes. The tool shows the selected size and the size below it with the reason that smaller size was rejected, so you can see how close the call was.
  6. Read the warnings before committing. Very low velocity traps air; very high velocity causes noise and erosion.

This is preliminary sizing. Final design must account for coil and equipment pressure drop, control valve authority, balancing, and any project specification that overrides these limits.

📖 Chilled Water Pipe Sizing Guide

The three-band sizing rule

Chilled water pipe sizing is not a single rule — it is three bands, and getting this wrong is the most common mistake in quick calculators:

  • 2″ and below — velocity governs. Limit to about 4 ft/s (1.2 m/s). Friction loss on small pipes runs far above 4 ft per 100 ft at this velocity, and that is accepted; branch runs are short.
  • Above 2″ — friction governs. Limit to about 4 ft of water per 100 ft (roughly 120 Pa/m) to keep pump energy sensible over long runs.
  • Large pipes — velocity governs again. From roughly 6″ upward the friction rule alone allows very high velocity. At 14″ a 4 ft per 100 ft target works out at about 14 ft/s, which is well into erosion-corrosion territory. A cap of 8 ft/s (2.4 m/s) takes over.

Without that third band a calculator will undersize mains badly. At 6,000 GPM the friction rule alone points at 14″, while the correct answer with the velocity cap applied is 20″ — two sizes larger.

Converting cooling load to flow rate

US: GPM = TR × 24 / ΔT(°F) ΔT = 10 °F → 2.4 GPM per TR (chilled water) ΔT = 8 °F → 3.0 GPM per TR (condenser water) Metric: L/s = kW / (4.187 × ΔT(°C)) 1 TR = 3.51685 kW Friction (Darcy-Weisbach): h_f = f × (L/D) × v² / 2g Friction factor (Swamee-Jain, explicit Colebrook fit): f = 0.25 / [ log₁₀( ε/3.7D + 5.74/Re^0.9 ) ]² Re = v·D/ν ε = 0.045 mm steel, 0.0015 mm copper

A higher ΔT means less flow for the same tonnage, which means smaller pipes and lower pump energy. Moving a chilled water system from a 10 °F to a 16 °F ΔT cuts design flow by 37% and can drop the pipe two sizes — this is the core idea behind low-flow, high-ΔT plant design.

Recommended chilled water velocities

LocationVelocity (ft/s)Velocity (m/s)Notes
Pipe 2″ and below2 – 40.6 – 1.2Velocity governs; friction runs high and is accepted
Branch and riser4 – 71.2 – 2.1Friction limit usually governs
Mains and headers6 – 81.8 – 2.4Velocity cap governs from about 6″ upward
Pump suction4 – 71.2 – 2.1Keep low to protect NPSH available
Absolute maximum, steel103.0Above this, erosion-corrosion and flow noise
Minimum, any size20.6Below this, air and sediment will not be carried out

Why velocity and friction both matter

Velocity drives noise, vibration and erosion. In steel pipe, sustained velocity above about 10 ft/s strips the protective oxide layer at bends and tees and accelerates wall loss. In copper the practical limit is lower still, around 8 ft/s for cold water and 5 ft/s where the water is warm.

Friction drives pump head, and pump energy runs 24/7 for the life of the building. Halving the design friction rate roughly halves the piping share of pump head, at the cost of a larger pipe, more insulation and more support steel. The 4 ft per 100 ft target is the long-standing compromise between the two.

Typical applications

  • CHW mains, risers and headers in plant rooms
  • AHU and FCU chilled water coil connections
  • Primary / secondary and variable primary chilled water systems
  • Condenser water between chillers and cooling towers
  • District cooling distribution and ETS connections

Frequently asked questions

How do you size a chilled water pipe?
Convert the load to a flow rate, then pick the smallest pipe that stays inside the limits: 4 ft/s for 2″ and below, and 4 ft per 100 ft with an 8 ft/s cap above 2″. The calculator above does all three bands and shows which one governed.
How many GPM per ton for chilled water?
2.4 GPM per TR at the usual 10 °F ΔT, because GPM = TR × 24 ÷ ΔT(°F). Condenser water is normally taken at 3 GPM per TR, which corresponds to an 8 °F ΔT. In metric, 1 TR = 3.517 kW and L/s = kW ÷ (4.187 × ΔT°C).
What size chilled water pipe do I need for 100 tons?
100 TR at 10 °F ΔT is 240 GPM, which needs a 4″ Schedule 40 steel pipe — velocity 6.05 ft/s and friction 3.28 ft per 100 ft, both inside the limits. A 3″ line would run at 10.8 ft/s, far past the 8 ft/s cap.
What is the maximum velocity for chilled water pipes?
About 4 ft/s at 2″ and below, and 8 ft/s above that. Ten ft/s is the practical ceiling for steel before erosion-corrosion and noise become real problems. Condenser water in a plant room is sometimes allowed up to 10 ft/s.
What friction loss should be used for chilled water pipe sizing?
4 ft of water per 100 ft (about 120 Pa/m) for pipes above 2″. Lower friction means a bigger pipe with higher installed cost but lower pump energy; higher friction means a smaller pipe you will pay for in pumping every hour of every year.
Can I use this for condenser water or hot water?
Yes — switch the fluid selector. It changes the design temperature, the default ΔT and the velocity limits. Temperature matters because water viscosity varies by roughly four times between 45 °F chilled water and 180 °F heating water, and that changes the friction factor.
Does the calculator handle copper as well as steel?
Yes. Type L copper to ASTM B88 has a smaller bore than Schedule 40 steel at the same nominal size — 2″ Type L is 1.985″ internal against 2.067″ for steel — but copper is much smoother, so friction is lower at the same velocity. On borderline flows the two materials sometimes land on different sizes.
Is this suitable for final construction design?
It is intended for preliminary sizing and quick checks. Final design must add coil and equipment pressure drop, control valve authority, strainers, balancing devices, and any project specification that sets different limits.

Related tools: TR to CFM Calculator · Ductulator — Duct Size Calculator · Pump Head Calculator

References

  • ASHRAE Handbook - Fundamentals, Ch.22 Pipe Sizing
  • ASHRAE Handbook - HVAC Systems and Equipment
  • Carrier System Design Manual, Part 3 - Piping Design
  • ASME B36.10M - Welded and Seamless Wrought Steel Pipe
  • ASTM B88 - Seamless Copper Water Tube

Last updated: 2026-07-26