Find the pressure lost in a fire protection pipe with the Hazen-Williams formula NFPA 13 uses. Choose the pipe schedule and size, count the fittings — their equivalent lengths come from the NFPA 13 chart and are corrected for C-factor and wall thickness — add the elevation change, and read friction loss, velocity and the pressure needed at the inlet in US or metric units.
NFPA 13, NFPA 14 and NFPA 24 calculate friction loss in water-filled fire protection pipe with the Hazen-Williams formula. It needs only the flow, the internal diameter and a roughness coefficient C, which is why it is the standard method for sprinkler, standpipe and fire main calculations.
Two things follow from the exponents. Friction rises with flow to the power 1.85, so doubling the flow gives about 3.6 times the loss. And it falls with diameter to the power 4.87, so one pipe size up typically cuts the loss by half to two thirds — the cheapest fix for a calculation that does not work.
| Pipe or tube | C | Loss compared with C = 120 |
|---|---|---|
| Black or galvanized steel — dry pipe and preaction systems | 100 | × 1.40 |
| Unlined cast or ductile iron | 100 | × 1.40 |
| Black or galvanized steel — wet pipe and deluge systems | 120 | × 1.00 |
| Cement-lined cast or ductile iron, concrete | 140 | × 0.75 |
| Copper tube, brass, stainless steel | 150 | × 0.66 |
| Listed plastic pipe (CPVC), HDPE | 150 | × 0.66 |
Steel pipe in dry and preaction systems uses C = 100 because the alternately wet and dry pipe wall corrodes and roughens faster. The loss multiplier is (120 ÷ C)1.85.
| Flow | 2 in | 2½ in | 3 in | 4 in | 6 in | 8 in |
|---|---|---|---|---|---|---|
| 100 gpm (379 L/min) | 9.40 | 3.95 | 1.37 | 0.37 | 0.05 | 0.01 |
| 250 gpm (946 L/min) | — | 21.54 | 7.48 | 1.99 | 0.27 | 0.07 |
| 500 gpm (1,893 L/min) | — | — | — | 7.18 | 0.98 | 0.26 |
| 750 gpm (2,839 L/min) | — | — | — | 15.20 | 2.07 | 0.54 |
| 1,000 gpm (3,785 L/min) | — | — | — | — | 3.52 | 0.92 |
| 1,500 gpm (5,678 L/min) | — | — | — | — | 7.45 | 1.96 |
| 2,000 gpm (7,570 L/min) | — | — | — | — | — | 3.33 |
A dash means the velocity would exceed 20 ft/s (6.1 m/s). Multiply psi per 100 ft by 0.226 for bar per 100 m. Internal diameters: 2.067, 2.469, 3.068, 4.026, 6.065 and 7.981 in.
Each fitting is treated as an extra length of straight pipe that causes the same loss. The chart is written for Schedule 40 steel pipe at C = 120, in feet:
| Nominal size | 45° elbow | 90° standard elbow | 90° long-turn elbow | Tee or cross (turn) | Butterfly valve | Gate valve | Swing check |
|---|---|---|---|---|---|---|---|
| 1 in (DN25) | 1 | 2 | 2 | 5 | — | — | 5 |
| 1¼ in (DN32) | 1 | 3 | 2 | 6 | — | — | 7 |
| 1½ in (DN40) | 2 | 4 | 2 | 8 | — | — | 9 |
| 2 in (DN50) | 2 | 5 | 3 | 10 | 6 | 1 | 11 |
| 2½ in (DN65) | 3 | 6 | 4 | 12 | 7 | 1 | 14 |
| 3 in (DN80) | 3 | 7 | 5 | 15 | 10 | 1 | 16 |
| 4 in (DN100) | 4 | 10 | 6 | 20 | 12 | 2 | 22 |
| 5 in (DN125) | 5 | 12 | 8 | 25 | 9 | 2 | 27 |
| 6 in (DN150) | 7 | 14 | 9 | 30 | 10 | 3 | 32 |
| 8 in (DN200) | 9 | 18 | 13 | 35 | 12 | 4 | 45 |
| 10 in (DN250) | 11 | 22 | 16 | 50 | 19 | 5 | 55 |
| 12 in (DN300) | 13 | 27 | 18 | 60 | 21 | 6 | 65 |
The same flow in 4 in Schedule 10 pipe (4.260 in) loses only 0.0545 psi/ft — 24% less — which is why thin-wall pipe is common in sprinkler mains. To get the flow in the first place, use the Sprinkler Density Calculator or the Sprinkler K-Factor Calculator; add up the segments and carry the total to the Fire Pump Selection Calculator. The step-by-step method for a whole system is in the Fire Fighting System Design Calculation guide.
In US units, friction loss in psi per foot is p = 4.52 × Q^1.85 ÷ (C^1.85 × d^4.87), with Q in gpm and the internal diameter d in inches. In metric units, p in bar per metre is 6.05 × 10^5 × Q^1.85 ÷ (C^1.85 × d^4.87), with Q in L/min and d in mm. Multiply by the pipe length plus the equivalent length of fittings.
NFPA 13 gives C = 120 for black or galvanized steel in wet pipe and deluge systems, C = 100 for steel in dry pipe and preaction systems and for unlined cast or ductile iron, C = 140 for cement-lined ductile iron and C = 150 for copper, stainless steel and listed plastic pipe.
NFPA 13 sets no general velocity limit for hydraulically calculated systems. Many project specifications, insurers and authorities limit velocity to 20 ft/s (6.1 m/s) in sprinkler piping, and some allow up to 32 ft/s (9.8 m/s). Fire pump suction pipe is kept lower, at 15 ft/s (4.6 m/s) at 150% of rated flow under NFPA 20.
Add the equivalent length of each fitting from the NFPA 13 chart to the pipe length. A 4 in standard 90° elbow counts as 10 ft and a 4 in tee with the flow turning as 20 ft. Multiply the chart value by 0.713 for C = 100 or 1.51 for C = 150, and by (actual ID ÷ Schedule 40 ID)^4.87 for pipe that is not Schedule 40.
Water loses 0.433 psi for every foot it rises — 0.098 bar per metre — and gains the same amount going down. A sprinkler 30 ft above the pump needs 13 psi more at the pump than one at the same level, whatever the flow.
Yes. Schedule 10 pipe has a thinner wall and a larger bore, and friction falls with diameter to the power 4.87. In 4 in pipe at 500 gpm, Schedule 40 loses 7.18 psi per 100 ft and Schedule 10 loses 5.45 psi per 100 ft, about 24% less.
Hazen-Williams is valid for water at ordinary temperatures. NFPA 13 requires the Darcy-Weisbach formula for antifreeze systems larger than 40 gal (151 L), and NFPA 750 uses it for intermediate and high pressure water mist systems, because viscosity and velocity are outside the range Hazen-Williams was fitted to.
Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.
Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.
No comments yet. Be the first to add one.