Duct Calculator: Air Duct Size Calculator

Free HVAC duct calculator. Enter any two of airflow, friction rate, velocity and diameter to size a round or rectangular air duct, in US or metric units, using the Darcy-Weisbach and Colebrook equations from the ASHRAE duct design method.

Inputs
Units

Tick any two of the four below; the other two are solved.

Duct size in X in
Calculated Results
Duct Sizing Notes

In equal friction duct design, you typically select a friction target (pressure loss per length) and size ducts so pressure drop stays uniform throughout the system. This helps balancing, keeps fan static predictable, and makes duct sizing consistent from main to branches.

When to Adjust Your Target

  • Noise issue: reduce velocity (bigger duct) or reduce friction target.
  • High fan static: lower friction target in long mains and long runs.
  • Space constraints: allow slightly higher friction but keep AR reasonable.

Good Practice Checklist

  • Confirm total static includes fittings (elbows, transitions, dampers, coils, filters).
  • Prefer standard duct sizes where possible.
  • Consider insulation thickness and clearance before finalizing sizes.
Quick Checks (Design Validation)

Aspect Ratio

  • Try to keep AR ≤ 4:1 for easy fabrication and lower noise.
  • If space forces high AR (e.g., 6:1), consider reducing velocity.
  • Very flat ducts can increase losses and noise.

Noise & Velocity

  • Near diffusers: supply typically 500–900 fpm.
  • Main trunks can be higher, but watch noise limits.
  • If VP looks high, reduce friction target / velocity.

Pressure Drop Strategy

  • Long runs → lower friction (e.g., 0.06–0.08) reduces fan static.
  • Short runs / tight shafts → slightly higher friction can be acceptable.
  • Also check fittings (elbows, transitions, dampers).

Practical Notes

  • Prefer standard sizes; avoid odd dimensions where possible.
  • Check insulation thickness (space clearance).
  • Confirm access doors, turning vanes, balancing dampers.

How to Use (Short)

  1. Select US/Metric and Air Condition.
  2. Enter any 2 values (Flow + Friction is common).
  3. Enter Height to calculate Width; verify aspect ratio.
  4. Review velocity and VP; adjust friction target if needed.
How This Duct Calculator Works

The calculator uses the Darcy-Weisbach equation with the Colebrook friction factor, the method in the ASHRAE Handbook duct design chapter. Rectangular ducts are matched to round by the ASHRAE equivalent diameter, De = 1.30 × (a × b)0.625 / (a + b)0.25, so both have the same friction loss at the same airflow.

Example: 1,000 CFM Supply Duct

At a friction rate of 0.10 in.wg per 100 ft, 1,000 CFM calculates to about 13.7–13.9 in diameter (depending on the roughness setting), so you would use a 14 in round duct, which runs at about 935 fpm. If the ceiling void allows only 10 in of height, enter 10 in as the height and the calculator returns a width of about 16 in. The aspect ratio of 1.6:1 is comfortably below 4:1.

Typical Design Values

Duct sectionFriction rateVelocity
Commercial supply main0.08–0.10 in.wg/100 ft (0.65–0.85 Pa/m)1,000–1,500 fpm (5–7.5 m/s)
Branch supply0.08–0.10 in.wg/100 ft600–900 fpm (3–4.5 m/s)
Return duct0.05–0.08 in.wg/100 ft600–1,000 fpm (3–5 m/s)
Residential main0.08–0.10 in.wg/100 ft700–900 fpm (3.5–4.5 m/s)

Need standard duct sizes, a CFM to duct size chart or air density correction? Use the Online Ductulator. For the total fan pressure, see the Fan Static Pressure Calculator. Printable tables are in the Duct Size Chart PDF, and the two sizing methods are compared in Equal Friction vs Velocity Method.

Duct Calculator FAQ
What is a duct calculator?

A duct calculator sizes HVAC air ducts from the airflow and a design limit, either a friction rate (pressure loss per length) or a maximum velocity. Enter any two of airflow, friction, velocity and diameter and it returns the other two, plus the equivalent rectangular size.

How do I calculate duct size from CFM?

Choose a friction rate, typically 0.08 to 0.10 in.wg per 100 ft for supply ducts, then find the diameter whose friction loss at that airflow matches it. For example, 1,000 CFM at 0.10 in.wg per 100 ft calculates to about 13.7 to 13.9 inches, so a 14 inch round duct (about 935 fpm) or a 16 by 10 inch rectangular duct is used.

What friction rate should I use?

0.08 to 0.10 in.wg per 100 ft (about 0.65 to 0.85 Pa/m) for supply ducts and 0.05 to 0.08 for returns in typical comfort systems. Use a lower rate on long runs to keep fan static pressure down.

What velocity is acceptable in air ducts?

Typical design velocities are 700 to 900 fpm for residential mains, 1,000 to 1,500 fpm for commercial supply mains and 600 to 900 fpm for branches. Use the lower end near noise-sensitive rooms.

What is the difference between this duct calculator and a ductulator?

Both size ducts with the same physics. This duct calculator solves any two of four values and shows Reynolds number and friction factor. The Online Ductulator adds standard size selection, a CFM to duct size chart, air density correction and rectangular to round converters.

References
  • ASHRAE Handbook - Fundamentals (Duct Design)
  • SMACNA HVAC Duct Construction Standards
  • ASHRAE 62.1 - Ventilation Standards

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.