Hydrant Flow Test Calculator: Available Fire Flow (NFPA 291)

Convert a hydrant flow test into the fire flow the water main can deliver. Enter the static and residual pressures and either the pitot reading with the outlet size and coefficient, or a measured flow; the calculator gives the test flow, the flow available at 20 psi (1.4 bar) or any other residual pressure, the supply curve, a table of flow against pressure and the NFPA 291 hydrant capacity class.

NFPA 291NFPA 24AWWA M17

Inputs

1

Pressures at the residual hydrant

Before any hydrant is flowing
While the flow hydrant is open
2

Flow at the flow hydrant

Measure the actual opening
With the same pitot reading
3

Flow wanted at

20 psi (1.4 bar) is the NFPA 291 rating basis

How a Hydrant Flow Test Works

A flow test measures how much water a main can deliver and how far the pressure falls when it does. It uses at least two hydrants: a residual hydrant, fitted with a pressure gauge and not flowed, and one or more flow hydrants downstream of it.

  1. Read the static pressure on the residual hydrant with no water flowing.
  2. Open the flow hydrant fully and wait for the reading to steady.
  3. Read the residual pressure on the residual hydrant and the pitot pressure in the stream at the flow hydrant at the same time.
  4. Close the hydrant slowly, convert the pitot reading to flow, and extend the result to the pressure you are interested in.

Hold the pitot tip in the centre of the stream, about half the outlet diameter away from the opening, with the air bled out of the gauge. Flow enough outlets to pull the residual pressure down by at least 25% of the static, or to reach the fire flow you need to prove — a small drop gives an unreliable extrapolation.

Hydrant Flow Test Formulas (NFPA 291)

Outlet flow: Q = 29.84 × c × d² × √p (gpm · d in inches · p = pitot pressure in psi)
Metric: Q = 0.0666 × c × d² × √p (L/min · d in mm · p in kPa)

Available flow: QR = QF × (hr ÷ hf)0.54
hr = static − desired residual · hf = static − residual measured in the test

QF is the total flow measured during the test and QR the flow predicted at the desired residual pressure, normally 20 psi (1.4 bar). The exponent 0.54 comes from the Hazen-Williams relationship: pressure loss in the mains is proportional to flow to the power 1.85, and 1 ÷ 1.85 = 0.54. Plotted on N1.85 graph paper the supply is a straight line through the static point and the test point.

Pitot Pressure to GPM: 2½ in Hydrant Outlet

Pitot pressurec = 0.90 (smooth, rounded)c = 0.80 (square, sharp)c = 0.70 (projecting into barrel)
5 psi (0.34 bar)375 gpm334 gpm292 gpm
10 psi (0.69 bar)531 gpm472 gpm413 gpm
15 psi (1.03 bar)650 gpm578 gpm506 gpm
20 psi (1.38 bar)751 gpm667 gpm584 gpm
25 psi (1.72 bar)839 gpm746 gpm653 gpm
30 psi (2.07 bar)919 gpm817 gpm715 gpm
40 psi (2.76 bar)1,062 gpm944 gpm826 gpm
50 psi (3.45 bar)1,187 gpm1,055 gpm923 gpm

Feel the inside edge of the outlet to pick the coefficient: a smooth, rounded entry is 0.90, a square, sharp edge 0.80, and an outlet nipple that projects into the hydrant barrel 0.70. Readings between 10 and 30 psi are the most accurate. For 4 in and larger pumper outlets NFPA 291 applies a further correction to the pitot flow — 0.83 at 7 psi and above, rising to 0.97 at 2 psi — because the stream does not fill the outlet evenly.

NFPA 291 Hydrant Capacity Classes and Colours

ClassRated capacity at 20 psi (1.4 bar) residualBonnet and cap colour
AA1,500 gpm (5,680 L/min) or moreLight blue
A1,000 – 1,499 gpm (3,785 – 5,675 L/min)Green
B500 – 999 gpm (1,900 – 3,780 L/min)Orange
CLess than 500 gpm (1,900 L/min)Red

The 20 psi basis leaves enough pressure in the main to supply a fire engine's suction without risking negative pressure — and backflow or pipe collapse — elsewhere in the network. NFPA 291 recommends chrome yellow barrels for public hydrants and repeating flow tests about every five years.

Using the Result for Sprinkler and Fire Pump Design

The three numbers from the test — static pressure, residual pressure and the flow at that residual — define the water supply curve for a hydraulic calculation. The system demand point (flow and pressure at the connection) must fall below the curve, usually with a safety margin of 10% or 10 psi to allow for seasonal lows and future growth. If it does not, the options are larger pipe, a different connection point, a fire pump, or a storage tank. Correct the test pressures for any difference in elevation between the residual hydrant and the building connection (0.433 psi per foot).

Worked Example

  1. Static pressure 65 psi; residual with one 2½ in outlet flowing 45 psi — a drop of 20 psi, 31% of static.
  2. Pitot reading 20 psi on a smooth outlet (c = 0.90): Q = 29.84 × 0.90 × 2.5² × √20 = 751 gpm (2,841 L/min).
  3. hf = 65 − 45 = 20 psi; hr = 65 − 20 = 45 psi.
  4. QR = 751 × (45 ÷ 20)0.54 = 751 × 1.549 = 1,163 gpm (4,403 L/min) at 20 psi.
  5. Rated capacity 1,000–1,499 gpm → Class A, green.

Use the friction loss in the service pipe from the Fire Hydraulic Calculator to carry the supply curve to the base of the riser, and compare it with the demand from the Sprinkler Density Calculator.

Frequently asked questions

How do you calculate GPM from a pitot pressure reading?

Q = 29.84 × c × d² × √p, where c is the outlet coefficient, d the outlet diameter in inches and p the pitot pressure in psi. A 2½ in outlet with a smooth entry (c = 0.90) and a 20 psi pitot reading flows 29.84 × 0.90 × 6.25 × 4.47 = 751 gpm.

What is the formula for available fire flow at 20 psi?

NFPA 291 uses Q_R = Q_F × ((static − 20) ÷ (static − residual))^0.54, where Q_F is the flow measured in the test. With 65 psi static, 45 psi residual and 751 gpm flowing, the flow available at 20 psi is 751 × (45 ÷ 20)^0.54 = 1,163 gpm.

Why is hydrant flow rated at 20 psi residual?

20 psi (1.4 bar) is the lowest pressure normally allowed in a public main during fire fighting. It leaves enough to feed a fire engine through its suction hose and keeps the rest of the network above atmospheric pressure, avoiding backflow of contaminated water and damage to the pipes.

What do the colours on fire hydrant caps mean?

Under NFPA 291 the bonnet and caps show the capacity at 20 psi: light blue is Class AA, 1,500 gpm or more; green is Class A, 1,000–1,499 gpm; orange is Class B, 500–999 gpm; red is Class C, below 500 gpm. Some water authorities use their own colour scheme.

What is the difference between static and residual pressure?

Static pressure is the pressure in the main with no test water flowing. Residual pressure is the pressure remaining at the same gauge while the flow hydrant is discharging. The difference between them shows how much the supply is strained by that flow.

How much pressure drop is needed for a valid flow test?

NFPA 291 recommends flowing enough water to drop the residual pressure by at least 25% of the static pressure, or to reach the total fire flow required. With a smaller drop, small gauge errors are magnified when the result is extended to 20 psi, so open another outlet or another hydrant.

How often should hydrants be flow tested?

NFPA 291 recommends a flow test about every five years to confirm the capacity and colour marking of each hydrant. A new test is also needed whenever a sprinkler or fire pump design relies on the supply and the last data are more than about a year old, or the network has changed.

References & standards

  • NFPA 291 - Recommended Practice for Water Flow Testing and Marking of Hydrants (test procedure, pitot formula and outlet coefficients, rated capacity at 20 psi, capacity classes and colours)
  • NFPA 24 - Standard for the Installation of Private Fire Service Mains and Their Appurtenances
  • AWWA Manual M17 - Fire Hydrants: Installation, Field Testing and Maintenance
  • NFPA 13 - Standard for the Installation of Sprinkler Systems (water supply information for hydraulic calculations)

Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.