HVAC E20 Heat Load Calculator: Room Cooling Load

Estimate the cooling load of a room the way the E20 form does it: heat gain through walls, roof and glass, solar gain, people, lighting, equipment and fresh air, added up at the design condition. The calculator shows every component, the sensible and latent totals, the load in kW, TR and Btu/h and the supply airflow — in metric or US units.

ASHRAE FundamentalsCarrier E20 formASHRAE 62.1

Inputs

1

Building envelope

Net of windows
Clear double 0.6–0.7 · low-e / tinted 0.25–0.4 · with blinds lower
Peak on the exposed façade
0 if another floor is above
e.g. 39 °C outside − 24 °C inside = 15 °C
2

Internal loads

Seated office work is about 75 W sensible + 55 W latent per person; light activity or retail 75 + 75; gym 210 + 315.
LED offices 6–10 W/m²
Offices 10–15 W/m²
3

Fresh air and safety

10 L/s (20 CFM) per person is typical
Outdoor − indoor humidity ratio

The E20 Method in Brief

"E20" is the name of Carrier's classic cooling-load estimate form: a one-page sheet that lists every heat gain to a room — through the envelope, from the sun, from people, lights and equipment, and from outdoor air — and adds them up at the design hour. It remains the quickest way to size a room air conditioner or check a software result by hand.

Conduction (walls, roof, glass): Q = U × A × ΔT
Solar through glass: Q = A × SHGC × solar irradiance
People: Q = number × (sensible + latent per person)
Lighting and equipment: Q = installed watts × usage
Fresh air: Qs = 1.2 × L/s × ΔT · Ql = 3.0 × L/s × Δw (g/kg) [US: 1.08 × CFM × ΔT°F · 0.68 × CFM × Δgr/lb]
Total = (sum of sensible + latent) × (1 + safety factor) · 1 TR = 3.517 kW = 12,000 Btu/h

Typical Input Values

ItemTypical valueUS units
Insulated wall, U-value0.3 – 0.6 W/m²K0.05 – 0.10 Btu/h·ft²·°F
Uninsulated block or concrete wall1.5 – 2.5 W/m²K0.26 – 0.44
Insulated roof0.2 – 0.4 W/m²K0.035 – 0.07
Double glazing / low-e double glazing2.8 – 3.0 / 1.6 – 2.0 W/m²K0.49 – 0.53 / 0.28 – 0.35
Single glazing5.7 W/m²K1.0
Peak solar on vertical glass (east / west)500 – 700 W/m²160 – 220 Btu/h·ft²
Peak solar on shaded or north-facing glass*100 – 200 W/m²30 – 65 Btu/h·ft²
Person, seated office work75 W sensible + 55 W latent250 + 200 Btu/h
Lighting, LED office6 – 10 W/m²0.6 – 0.9 W/ft²
Office equipment10 – 15 W/m²0.9 – 1.4 W/ft²
Fresh air per person8 – 10 L/s17 – 20 CFM

*North-facing in the northern hemisphere. The U-value conversion is 1 Btu/h·ft²·°F = 5.678 W/m²K. Take design temperatures from ASHRAE climatic data or the local code, and the ventilation rate from ASHRAE 62.1.

Sensible, Latent and the Sensible Heat Ratio

Sensible gains raise the air temperature; latent gains add moisture, which the coil must condense. Their split matters as much as the total: the sensible heat ratio (SHR = sensible ÷ total) tells you what kind of coil is needed. Offices run at 0.80–0.90; a crowded hall or a room with a lot of humid outdoor air may fall to 0.65–0.70 and needs a deeper coil or dedicated outdoor air treatment. The supply airflow is set by the sensible load: L/s = sensible W ÷ (1.2 × ΔT), about 75 L/s per kW of sensible load at an 11 °C difference (the familiar 400 CFM per ton assumes roughly 70% of the load is sensible).

Worked Example: Small Office Room

  1. Walls: 50 m² × 0.5 W/m²K × 15 K = 375 W.
  2. Windows: conduction 10 m² × 3.0 × 15 = 450 W; solar 10 × 0.4 × 300 W/m² = 1,200 W.
  3. Roof: none (occupied floor above).
  4. People: 5 × (75 + 55) = 650 W (375 sensible + 275 latent).
  5. Lighting 500 W and equipment 300 W.
  6. Subtotal = 3,475 W; with a 10% safety factor = 3,823 W = 3.82 kW = 1.09 TR = 13,043 Btu/h.
  7. Sensible heat ratio = 3,200 ÷ 3,475 = 0.92; supply air ≈ 265 L/s (562 CFM) at an 11 °C difference.

Adding 50 L/s of fresh air at the same 15 K difference and a 6 g/kg moisture difference brings another 905 W sensible and 900 W latent — a 52% increase, which is why outdoor air should never be left out in a humid climate. For a multi-zone calculation use the Cooling & Heat Load Calculator; for a quick room estimate the Room Heat Load Calculator; then convert the result with the TR to CFM Calculator. The method is explained step by step in the HVAC load calculation guide.

Frequently asked questions

What is the E20 heat load method?

E20 is Carrier's cooling load estimate form. It lists each heat gain to a space — conduction through walls, roof and glass, solar gain through windows, people, lighting, equipment and outdoor air — calculates each one at the design condition and adds them, with a safety factor, to give the cooling load in watts, Btu/h or tons.

How do you calculate the cooling load of a room?

Add the heat gains: U × area × temperature difference for each wall, roof and window; window area × SHGC × solar irradiance; number of people × heat per person; lighting and equipment watts; and the fresh air load. Apply a safety factor of about 10% and divide by 3,517 to convert watts to tons of refrigeration.

How much heat does a person give off?

A seated adult doing office work gives off about 130 W in total — roughly 75 W sensible and 55 W latent (250 and 200 Btu/h). Light activity raises it to about 150 W, and heavy exercise to more than 500 W, most of it latent.

How do I convert watts to tons of refrigeration?

Divide watts by 3,517, or kW by 3.517. A 3,823 W load is 1.09 TR. In US units, divide Btu/h by 12,000: 13,043 Btu/h is also 1.09 tons.

What safety factor should be added to a heat load?

5–10% is normal for a careful calculation. Larger factors only oversize the equipment, which then cycles, controls humidity poorly and costs more to run. Do not add a safety factor on top of inputs that are already conservative.

How is the fresh air load calculated?

Sensible load in watts = 1.2 × airflow in L/s × temperature difference in °C; latent load = 3.0 × L/s × humidity ratio difference in g/kg. In US units: 1.08 × CFM × ΔT in °F and 0.68 × CFM × difference in grains per pound.

References & standards

  • ASHRAE Handbook - Fundamentals (nonresidential cooling and heating load calculations, heat gain from occupants, lighting and equipment)
  • Carrier System Design Manual, Part 1 - Load Estimating (E20 cooling load estimate form)
  • ANSI/ASHRAE Standard 62.1 - Ventilation and Acceptable Indoor Air Quality
  • ASHRAE climatic design conditions for the project location

Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.