Electrical Load Current Calculator ⚡

Convert kW, HP or kVA to amps for single-phase and three-phase systems, accounting for power factor and motor efficiency. Aligned with NEC Article 430 and IEC 60364.

📊 Input

kW/HP are treated as shaft output (efficiency applied). kVA is electrical apparent power.
~1.0 for heaters, 0.8–0.9 for motors
Use 100% for electrical input / kVA

📊 Results

Enter power and click Calculate

📚 References

How to Calculate Electrical Load Current

Load current is the amount of current a piece of equipment draws from the supply. You need it to size cables, breakers, contactors and transformers, and to check that an existing circuit isn't overloaded. This guide shows the formulas, the role of power factor and efficiency, and how to read the results above.

The Core Formulas

Three-phase:  I = (kW × 1000) ÷ (√3 × V × PF)
Single-phase:  I = (kW × 1000) ÷ (V × PF)

From kVA (3-phase):  I = (kVA × 1000) ÷ (√3 × V)
From HP:  kW = HP × 0.7457 ÷ efficiency

V is the line-to-line voltage for three-phase systems and the line-to-neutral voltage for single-phase. PF is power factor (0–1). For three-phase the √3 (≈1.732) accounts for the phase relationship between the three line currents.

Power Factor — Why It Increases Current

Power factor is the ratio of real power (kW, the useful work) to apparent power (kVA, what the supply must actually provide). Inductive loads like motors draw extra reactive current that does no work but still heats cables. A motor running at PF 0.8 draws about 25% more current than the same kW at unity power factor — so a poor power factor directly enlarges the cable and breaker you need.

Efficiency — Output vs Input Power

A motor nameplate usually states mechanical output power. The electrical input the supply must deliver is higher, because some energy is lost as heat. Input kW = output kW ÷ efficiency. A 10 kW motor at 92% efficiency actually draws about 10.9 kW of electrical power. That's why this calculator applies efficiency to kW and HP inputs — and why you should set it to 100% when entering electrical input power or kVA.

Motor Full-Load Current (NEC)

For motor circuit design, NEC requires using the table full-load current values (e.g. Table 430.250 for three-phase motors) rather than a calculated value, because manufacturers vary. The calculated figure here is excellent for estimating, transformer loading and energy studies, but for code-compliant motor protection use the NEC table current and the branch-circuit multipliers in Article 430.

Typical Full-Load Currents (3-Phase, 400 V, PF 0.85, ~92% eff.)

Motor (kW)Motor (HP)Approx. FLC (A)
0.751~1.6
1.52~3.1
3.75~7.6
7.510~15
1520~30
3040~59
5575~108
90120~177

Indicative values — actual current depends on nameplate efficiency, power factor and voltage. Verify against the manufacturer's data and the applicable code table.

Worked Example

A 22 kW (output) three-phase motor on 415 V, power factor 0.86, efficiency 93%:

Enter these values above to confirm, then click through to the cable size calculator to choose the conductor.

Common Mistakes

Frequently Asked Questions

How do I convert kW to amps?

For three-phase: Amps = (kW × 1000) ÷ (√3 × V × PF). For single-phase: Amps = (kW × 1000) ÷ (V × PF). V is line voltage and PF is the power factor. If the kW figure is a motor shaft (output) rating, divide by efficiency first to get electrical input power.

How do I convert HP to amps?

First convert horsepower to kilowatts (1 HP = 0.7457 kW), then divide by motor efficiency to get electrical input power, then apply the standard current formula. This calculator does all three steps automatically when you select HP.

What is the difference between kW and kVA?

kW is real (working) power; kVA is apparent power. They are linked by power factor: kW = kVA × PF. Current is most directly found from kVA because Amps = (kVA × 1000) ÷ (√3 × V) for three-phase, with no power factor needed.

Should I include efficiency?

Yes for motors, where the nameplate kW or HP is mechanical output — divide by efficiency (often 0.88–0.96) to get the electrical input the supply must deliver. Set efficiency to 100% if you are entering electrical input power directly, or when entering kVA.

Why does power factor matter?

Power factor is the ratio of real to apparent power. A lower power factor means more current is needed for the same useful power, increasing losses and cable size. Typical values are 0.8–0.9 for motors and near 1.0 for resistive (heating) loads.

Can I use the calculated current to size a breaker or cable?

It is a good starting point, but motor circuits follow special rules. NEC Article 430 uses table full-load currents and sizes branch-circuit protection above the running current. Always apply the relevant code factors and verify with the cable size calculator.