Wire Gauge Chart: AWG to mm² Conversion 📏

AWG and kcmil to mm² conversion with diameter, resistance and weight, NEC Table 310.16 ampacities, and metric cable sizes with their nearest AWG.

d (mm) = 0.127 × 92(36 − n)/39  ·  A (mm²) = π × d² / 4
Every 3 gauges halves the area · 1 kcmil = 0.5067 mm²

🔄 Quick AWG ↔ mm² Converter

—
Conversion result

AWG to mm² Chart

SizeDiameter (mm)Diameter (in)Area (mm²)Ω/km CuΩ/km AlCu weight (kg/km)
600 kcmil19.6750.7746304.020.05670.09302,702.8
500 kcmil17.9610.7071253.350.06810.11162,252.3
400 kcmil16.0640.6325202.680.08510.13941,801.9
350 kcmil15.0270.5916177.350.09720.15941,576.6
300 kcmil13.9120.5477152.010.11340.18591,351.4
250 kcmil12.7000.5000126.680.13610.22311,126.2
4/0 AWG11.6840.4600107.220.16080.2636953.2
3/0 AWG10.4050.409685.030.20280.3324755.9
2/0 AWG9.2660.364867.430.25570.4192599.5
1/0 AWG8.2510.324953.480.32240.5285475.4
1 AWG7.3480.289342.410.40660.6665377.0
2 AWG6.5440.257633.630.51270.8404299.0
3 AWG5.8270.229426.670.64641.060237.1
4 AWG5.1890.204321.150.81521.336188.0
6 AWG4.1150.162013.301.2962.125118.3
8 AWG3.2640.12858.372.0613.37974.4
10 AWG2.5880.10195.263.2775.37246.8
12 AWG2.0530.08083.315.2118.54229.4
14 AWG1.6280.06412.088.28513.58318.5
16 AWG1.2910.05081.3113.17421.59711.6
18 AWG1.0240.04030.82320.94834.3417.3
20 AWG0.8120.03200.51833.30854.6044.6
22 AWG0.6440.02530.32652.96286.8242.9
24 AWG0.5110.02010.20584.213138.0551.8

Solid conductor values at 20 °C. Stranded conductors have a slightly larger overall diameter for the same area. kcmil diameters are for the equivalent solid area.

Metric Cable Sizes to AWG

mm²Nearest AWG (by area)Nearest common sizeDiameter (mm)Ω/km CuAmpacity* (A)
0.520 AWG20 AWG0.8036—
0.7518 AWG18 AWG0.9824.5—
117 AWG18 AWG1.1318.1—
1.515 AWG16 AWG1.3812.117.5
2.513 AWG14 AWG1.787.4124
411 AWG12 AWG2.264.6132
69 AWG10 AWG2.763.0841
107 AWG8 AWG3.571.8357
165 AWG6 AWG4.511.1576
253 AWG3 AWG5.640.727101
352 AWG2 AWG6.680.524125
501/0 AWG1/0 AWG7.980.387151
702/0 AWG2/0 AWG9.440.268192
953/0 AWG3/0 AWG11.000.193232
120250 kcmil250 kcmil12.360.153269
150300 kcmil300 kcmil13.820.124309
185350 kcmil350 kcmil15.350.0991353
240500 kcmil500 kcmil17.480.0754415

"Nearest AWG" can be an odd gauge such as 13 AWG that is rarely stocked; "Nearest common size" picks from the sizes in the AWG table. * IEC 60364-5-52 / BS 7671, single-core PVC copper cables, reference method C (clipped direct), 30 °C, one circuit, the same values as the Cable Size Calculator. Resistance per IEC 60228 at 20 °C.

NEC Table 310.16 Ampacities (Copper, 30 °C)

AWG / kcmil60 °C (TW, UF)75 °C (THW, THWN)90 °C (THHN)
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475

Not more than three current-carrying conductors. NEC 240.4(D) limits overcurrent protection to 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.

How the AWG System Works

American Wire Gauge (AWG) is a logarithmic scale: a smaller number is a thicker wire. Every 3 gauges the cross-sectional area halves, and every 6 gauges the diameter halves. Sizes above 1 AWG continue as 1/0, 2/0, 3/0 and 4/0 (also written 0, 00, 000 and 0000), and anything larger is given in kcmil (thousand circular mils).

Metric cables are sold directly by cross-sectional area in mm² (1.5, 2.5, 4, 6, 10, 16 mm² and so on), so the two systems never line up exactly. When converting a design, pick the metric size whose area is equal to or larger than the AWG size, then check ampacity and voltage drop for the actual installation with the Cable Size Calculator and the Voltage Drop Calculator.

FAQ

What is 12 AWG in mm²?

12 AWG is 3.31 mm² (2.05 mm diameter). It sits between the metric sizes 2.5 mm² and 4 mm²; use 4 mm² as the metric equivalent so the conductor is not smaller.

What is 2.5 mm² in AWG?

2.5 mm² is closest to 13 AWG (2.63 mm²), a size rarely stocked. The common US sizes either side are 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²); choose 12 AWG when the conductor must be at least as large.

Does a higher AWG number mean a thinner wire?

Yes. Every 3 gauge numbers halves the cross-sectional area, and every 6 gauge numbers halves the diameter. 10 AWG has about twice the area of 13 AWG and four times the area of 16 AWG.

How do you convert AWG to mm²?

Diameter d = 0.127 mm × 92^((36 − n)/39), where n is the gauge number (use 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0). Then area = π × d² / 4. For 10 AWG, d = 2.588 mm and area = 5.26 mm².

What is kcmil?

One kcmil (thousand circular mils, also written MCM) is 0.5067 mm². Sizes larger than 4/0 AWG are given in kcmil, for example 250 kcmil = 126.7 mm² and 500 kcmil = 253.4 mm².

Which NEC ampacity column should I use?

Use the 75 °C column for most circuits, because equipment terminals are usually rated 75 °C (60 °C for many devices up to 100 A). The 90 °C column may be used for derating, but the result cannot exceed the termination rating.

📚 References

  • AWG diameter: d = 0.127 mm × 92^((36 − n)/39) (ASTM B258)
  • Resistance at 20 °C: copper 0.017241 Ω·mm²/m, aluminium 0.028264 Ω·mm²/m
  • NEC Table 310.16 - Allowable ampacities of insulated conductors
  • IEC 60228 - Conductors of insulated cables (metric resistance values)
  • IEC 60364-5-52 / BS 7671 Appendix 4 - current-carrying capacity, reference method C