Power Factor Calculator ⚡

Calculate power factor (PF), kVA, kVAR and phase angle (φ) for single-phase and three-phase systems, from kW, voltage and current, from kW and kVA, or convert kW to kVAR from a known power factor.

Power factor formula: PF = kW ÷ kVA = cos φ
Single phase: PF = P ÷ (V × I)  ·  Three phase: PF = P ÷ (√3 × VL-L × I)  (P in watts)

🧮 Inputs

Enter the actual power consumed by the load
Line-to-line voltage for 3-phase, line-to-neutral for single-phase
Line current for the system
Results update automatically as you type.
📈 Results
Power Factor:
0.00
Apparent Power (kVA):
0.00 kVA
Reactive Power (kVAR):
0.00 kVAR
Phase Angle (φ):
0.00°
Power Factor Type:
-

Power Factor Formula

Power factor: PF = kW / kVA = cos φ
Single-phase: kVA = (V × A) / 1000  →  PF = W / (V × A)
Three-phase: kVA = (√3 × V × A) / 1000  →  PF = W / (√3 × V × A)
Reactive power: kVAR = √(kVA² − kW²) = kW × tan φ
Phase angle: φ = arccos(PF)

In three-phase formulas, V is the line-to-line voltage and A is the line current. In single-phase formulas, V is line-to-neutral.

The Power Triangle

kW, kVAR and kVA form a right-angled triangle. Real power (kW) is the base, reactive power (kVAR) is the height, and apparent power (kVA) is the hypotenuse. The angle between kW and kVA is φ, and cos φ is the power factor.

φ Real power, kW kVAR Apparent power, kVA PF = cos φ = kW ÷ kVA

How to Calculate Power Factor (Step by Step)

  1. Measure or note the real power kW, the voltage and the current.
  2. Work out the apparent power: kVA = V × I / 1000 (single phase) or √3 × V × I / 1000 (three phase).
  3. Divide: PF = kW ÷ kVA.
  4. If you need them, find kVAR = √(kVA² − kW²) and φ = arccos(PF).

Worked Example 1: Single-Phase Load

A single-phase load draws 2.2 kW at 230 V and 12 A:

  1. kVA = (230 × 12) / 1000 = 2.76 kVA
  2. PF = 2.2 ÷ 2.76 = 0.80
  3. kVAR = √(2.76² − 2.2²) = 1.67 kVAR
  4. φ = arccos(0.80) = 37.1°

Worked Example 2: 50 kW Motor Panel (Three-Phase)

A three-phase panel reads 50 kW at 415 V with a measured line current of 87 A:

  1. kVA = (√3 × 415 × 87) / 1000 = 62.54 kVA
  2. PF = 50 ÷ 62.54 = 0.80
  3. kVAR = √(62.54² − 50²) = 37.56 kVAR
  4. φ = arccos(0.80) = 36.9°

Enter the same numbers above to see these steps generated automatically.

kW to kVAR and kVA to kVAR

If you already know the power factor, choose "kW and power factor" above, or use these formulas:

kVA = kW / PF
kVAR = kW × tan(arccos PF)
kVAR = kVA × sin(arccos PF)

Example: 100 kW at PF 0.85 → kVA = 100 / 0.85 = 117.6 kVA, kVAR = 100 × 0.620 = 62.0 kVAR. On a 415 V three-phase supply that is a line current of 163.7 A.

To raise the power factor, size the capacitor bank in kVAR with the Power Factor Correction Calculator, and convert between kW and kVA with the kW to kVA Calculator.

Why Low Power Factor Costs You Current

For the same 10 kW load on 415 V three-phase, the line current rises sharply as PF drops. This is why utilities penalise low PF and why cables, breakers and transformers must be oversized:

Power FactorLine Currentvs PF 1.0
1.0013.9 A—
0.9015.5 A+11%
0.8017.4 A+25%
0.7019.9 A+43%
0.6023.2 A+67%

Typical Power Factor Values

Load TypeTypical PF
Resistive heating / incandescent lighting1.00
Induction motor (full load)0.80 – 0.85
Induction motor (light load)0.50 – 0.70
LED drivers (quality)0.90 – 0.95
Fluorescent (magnetic ballast, uncorrected)0.50 – 0.60
Welding machines0.50 – 0.60

Measured panel PF matters for feeder sizing. Build the full schedule with the Electrical Panel Load Calculator.

FAQ

What is the power factor formula?

PF = kW / kVA = cos φ. For single phase, kVA = V × I / 1000, so PF = P / (V × I). For three phase, kVA = √3 × V × I / 1000, so PF = P / (√3 × V × I), with P in watts, V line-to-line and I the line current.

How do you calculate power factor for three phase?

Measure kW, line-to-line voltage and line current. Calculate kVA = 1.732 × V × I / 1000, then PF = kW / kVA. Example: 50 kW at 415 V and 87 A gives kVA = 62.54 and PF = 0.80.

How do I convert kW to kVAR?

kVAR = kW × tan(arccos PF). Example: 100 kW at PF 0.85 gives kVAR = 100 × 0.620 = 62.0 kVAR, and kVA = 100 / 0.85 = 117.6 kVA.

What is power factor?

Power factor is the ratio of real power (kW) doing useful work to apparent power (kVA) drawn from the supply. A PF of 1.0 means all current does useful work; at PF 0.7 a load draws about 43% more current than at PF 1.0.

What is a good power factor?

0.95 or higher is a common design target. Many utilities apply penalty charges when average PF falls below about 0.90 (0.85 in some tariffs). Typical uncorrected values: induction motors 0.80–0.85 at full load, welders 0.5–0.6, resistive heating 1.0.

What is the difference between lagging and leading power factor?

Lagging: current lags voltage, typical for inductive loads (motors, transformers, reactors). Leading: current leads voltage, caused by capacitive loads or over-compensated capacitor banks. kW, V and I readings alone cannot show which one you have; a power analyser is needed.

📚 References

  • Power triangle relationships (kW, kVA, kVAR): PF = kW/kVA = cos φ
  • S = V×I (1φ), S = √3×V×I (3φ)
  • IEEE 141 (Red Book) - Electric Power Distribution for Industrial Plants
  • IEC 61000-3 series - power quality & reactive power
  • Utility tariff practice: PF penalty thresholds (typ. 0.85-0.90)

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.