Power Factor Calculator ⚡

Calculate Power Factor (PF), kVA, kVAR and phase angle (φ) from kW, voltage and current for single-phase and three-phase systems.

🧮 Inputs

Enter the actual power consumed by the load
Line-to-line voltage for 3-phase, line-to-neutral for single-phase
Line current for the system
Auto calculate enabled (no Calculate button).
📈 Results
Power Factor:
0.00
Apparent Power (kVA):
0.00 kVA
Reactive Power (kVAR):
0.00 kVAR
Phase Angle (φ):
0.00°
Power Factor Type:
-

How to Use

  1. Select Single Phase or Three Phase.
  2. Enter kW, Voltage, and Current.
  3. Results update automatically: PF, kVA, kVAR and phase angle.

Formulas Used

Single-phase: kVA = (V × A) / 1000
Three-phase: kVA = (√3 × V × A) / 1000
Power Factor: PF = kW / kVA = cos φ
Reactive Power: kVAR = √(kVA² − kW²)
Phase Angle: φ = arccos(PF)

Worked Example — 50 kW Motor Panel (3-Phase)

A three-phase panel reads 50 kW at 415 V with a measured line current of 87 A:

  1. kVA = (√3 × 415 × 87) / 1000 = 62.54 kVA
  2. PF = 50 ÷ 62.54 = 0.80
  3. kVAR = √(62.54² − 50²) = 37.56 kVAR
  4. φ = arccos(0.80) = 36.9°

Enter the same numbers above to see these steps generated automatically.

Why Low Power Factor Costs You Current

For the same 10 kW load on 415 V three-phase, the line current rises sharply as PF drops — this is why utilities penalise low PF and why cables, breakers and transformers must be oversized:

Power FactorLine Currentvs PF 1.0
1.0013.9 A
0.9015.5 A+11%
0.8017.4 A+25%
0.7019.9 A+43%
0.6023.2 A+67%

Running at a low PF? Size the capacitor bank in kVAR with our Power Factor Correction Calculator.

Typical Power Factor Values

Load TypeTypical PF
Resistive heating / incandescent lighting1.00
Induction motor (full load)0.80 – 0.85
Induction motor (light load)0.50 – 0.70
LED drivers (quality)0.90 – 0.95
Fluorescent (magnetic ballast, uncorrected)0.50 – 0.60
Welding machines0.50 – 0.60

Measured panel PF matters for feeder sizing — build the full schedule with our Electrical Panel Load Calculator.

FAQ

What is power factor?

Power factor is the ratio of real power (kW) doing useful work to apparent power (kVA) drawn from the supply: PF = kW / kVA = cos φ. A PF of 1.0 means all current does useful work; a low PF means the same kW load draws more current — at PF 0.7 a load draws about 43% more current than at PF 1.0.

What is the power factor formula?

PF = kW / kVA, where kVA = V × I / 1000 (single-phase) or √3 × V × I / 1000 (three-phase). kVAR = √(kVA² − kW²), and φ = arccos(PF). Example: 50 kW, 415 V 3-phase, 87 A → kVA 62.54, PF 0.80, kVAR 37.56, φ 36.9°.

Why does three-phase use √3?

In a balanced three-phase system, apparent power is calculated from line-to-line voltage and line current. The √3 (≈1.732) factor comes from the geometry between line and phase quantities: S = √3 × VL-L × Iline.

What is a good power factor?

0.95 or higher is a common design target. Many utilities apply penalty charges when average PF falls below about 0.90 (0.85 in some tariffs). Typical uncorrected values: induction motors 0.80–0.85 at full load, welders 0.5–0.6, resistive heating 1.0.

What is the difference between lagging and leading power factor?

Lagging — current lags voltage; typical for inductive loads (motors, transformers, reactors). Leading — current leads voltage; caused by capacitive loads or over-compensated capacitor banks. Most industrial plants run lagging and improve PF with capacitor banks sized in kVAR.

📚 References

  • Power triangle relationships (kW, kVA, kVAR): PF = kW/kVA = cos φ
  • S = V×I (1φ), S = √3×V×I (3φ)
  • IEEE 141 (Red Book) - Electric Power Distribution for Industrial Plants
  • IEC 61000-3 series - power quality & reactive power
  • Utility tariff practice: PF penalty thresholds (typ. 0.85-0.90)