Fire Water Tank Size Calculator

Size a fire water storage tank from the system demand and the duration the standard requires. Choose a sprinkler hazard class or standpipe arrangement to load the NFPA 13 or NFPA 14 flow, hose stream and duration, or enter your own demand; the result is the effective capacity in gallons, litres and cubic metres, the gross volume with the unusable allowance, and the water depth for a round or rectangular tank.

NFPA 13NFPA 14NFPA 20NFPA 22

Inputs

1

Fire water demand

Use the demand from the hydraulic calculation when you have it — it is normally higher than density × area.
2

Tank

Water below the suction / anti-vortex plate, sediment zone

How Fire Water Tank Capacity Is Calculated

A fire water tank must hold enough water to supply the largest fire protection demand for the whole duration the standard requires, without counting on refill. The calculation is one multiplication — the engineering is in choosing the right flow and the right duration.

Effective capacity = (system demand + hose stream) × duration
gallons = gpm × minutes · litres = L/min × minutes · m³ = litres ÷ 1,000
Gross volume = effective capacity + water that cannot be used (below the suction, sediment zone)
1 m³ = 264.2 US gal = 220.0 imperial gal · 1 US gal = 3.785 litres

The system demand is the flow from the hydraulic calculation of the most demanding sprinkler area, or the standpipe demand. The hose stream is the NFPA 13 allowance for fire-fighter hose lines, added at the point of connection. The duration depends on the hazard.

Minimum Fire Water Storage by System (NFPA 13 and NFPA 14)

SystemDemand + hoseDurationCapacity, US galCapacity, m³
Sprinklers — Light Hazard150 + 100 = 250 gpm30 min7,50028.4
Sprinklers — Ordinary Hazard Group 1225 + 250 = 475 gpm60–90 min28,500 – 42,750107.9 – 161.8
Sprinklers — Ordinary Hazard Group 2300 + 250 = 550 gpm60–90 min33,000 – 49,500124.9 – 187.4
Sprinklers — Extra Hazard Group 1750 + 500 = 1,250 gpm90–120 min112,500 – 150,000425.9 – 567.8
Sprinklers — Extra Hazard Group 21,000 + 500 = 1,500 gpm90–120 min135,000 – 180,000511.0 – 681.4
Standpipes Class I / III — one riser500 gpm30 min15,00056.8
Standpipes Class I / III — two risers750 gpm30 min22,50085.2
Standpipes Class I / III — three or more, sprinklered building1,000 gpm30 min30,000113.6
Standpipes Class I / III — three or more, not sprinklered1,250 gpm30 min37,500141.9

Sprinkler figures use the minimum density × area demand; the hydraulically calculated demand is normally 10–20% higher and should be used when available. The shorter sprinkler duration applies where waterflow and supervisory devices are electrically supervised and monitored at a constantly attended location. Storage occupancies, foam and water spray systems have their own demands.

Which Demand Governs in a Combined System?

  • Fully sprinklered building with standpipes: the tank is sized for the larger of the sprinkler demand (including hose stream) and the standpipe demand — they are not added together.
  • Partially sprinklered building: the sprinkler demand is added to the standpipe demand, because both may operate.
  • Several separate hazards on one site: size for the single largest demand, not the sum, unless the authority requires simultaneous operation.
  • Pump-based sizing: where a fire pump takes suction from the tank, many authorities and insurers size the tank on the pump rated flow — or on 150% of it, the flow the pump must reach on test — for the required duration. Check the local code and enter that flow under Custom demand.

Effective Volume, Gross Volume and Tank Details

Only the water between the overflow (or the lowest fill level) and the lowest level the pump can draw from counts. NFPA 22 requires an anti-vortex plate on the suction outlet so the pump does not pull air as the level falls; the water below it is not usable. Add freeboard above the overflow when setting the shell height. The calculator's unusable-volume allowance — 10% by default — covers these for preliminary sizing; replace it with the actual dimensions once the tank is detailed.

  • Refill: NFPA 22 calls for a fill connection able to refill the tank within 8 hours. For a 33,000 gal tank that is about 69 gpm (260 L/min).
  • Shared tanks: where the tank also serves domestic or process water, the fire reserve must be protected — for example by taking the other outlets from above the fire reserve level — so normal use cannot draw it down.
  • Divided tanks: two half-capacity tanks or a divided tank let one half stay in service during cleaning and repair; some codes require this above a certain size.
  • Pump suction: NFPA 20 requires a positive suction pressure at the pump — a horizontal pump must sit below the tank's lowest water level, otherwise a vertical turbine pump is used.

Worked Example: Ordinary Hazard Group 2 Warehouse Office Block

  1. Sprinkler demand: 0.20 gpm/ft² × 1,500 ft² = 300 gpm (1,136 L/min).
  2. Hose stream allowance for ordinary hazard: 250 gpm → total 550 gpm (2,082 L/min).
  3. Duration with supervised alarms: 60 minutes.
  4. Effective capacity = 550 × 60 = 33,000 gal = 124,919 litres = 124.9 m³.
  5. Gross volume with 10% unusable allowance = 36,300 gal (137.4 m³).
  6. Round tank 25 ft (7.62 m) diameter: plan area 491 ft², water depth = 4,853 ft³ ÷ 491 = 9.9 ft (3.01 m), plus freeboard.

Get the demand from the Sprinkler Density Calculator or the Standpipe Calculator, then select the pump with the Fire Pump Selection Calculator. For a pump room layout to go with the tank, see the fire pump room DWG.

Frequently asked questions

How do you calculate fire water tank capacity?

Multiply the fire protection demand flow by the required duration. Add the sprinkler demand and the hose stream allowance first: for ordinary hazard Group 2, 300 gpm + 250 gpm = 550 gpm, and 550 gpm × 60 minutes = 33,000 US gallons, which is 124.9 m³. Then add the water that cannot be drawn from the tank to get the gross volume.

How long must a fire water tank last?

NFPA 13 requires 30 minutes for light hazard sprinkler systems, 60–90 minutes for ordinary hazard and 90–120 minutes for extra hazard. NFPA 14 requires 30 minutes for standpipe systems. Local codes and insurers can require longer — 60, 90 or 120 minutes at the fire pump rated flow is common.

What size tank do I need for a 500 gpm fire pump?

At the rated flow, a 500 gpm (1,893 L/min) pump uses 15,000 gal (56.8 m³) in 30 minutes, 30,000 gal (113.6 m³) in 60 minutes and 45,000 gal (170.3 m³) in 90 minutes. If the authority sizes the tank on 150% of rated flow, multiply those volumes by 1.5.

Do I add the sprinkler and standpipe demands together?

Not in a fully sprinklered building: the water supply is sized for the larger of the sprinkler demand, including hose stream, and the standpipe demand. In a partially sprinklered building the sprinkler demand is added to the standpipe demand.

Can the fire water tank be shared with domestic water?

Yes, if the fire reserve cannot be used for anything else. The usual arrangement takes the domestic outlet from a level above the fire reserve, so only the water above that level is available for normal use. Many authorities still prefer or require a dedicated fire tank.

How fast must a fire water tank refill?

NFPA 22 requires a means of filling the tank within 8 hours. Divide the tank capacity by 480 minutes for the minimum fill rate: a 33,000 gal (124.9 m³) tank needs about 69 gpm (260 L/min).

How do I convert the tank volume between gallons, litres and cubic metres?

One US gallon is 3.785 litres, so 1 m³ (1,000 litres) is 264.2 US gallons or 220.0 imperial gallons. A 30,000 US gal tank holds 113,562 litres, or 113.6 m³.

References & standards

  • NFPA 13 - Standard for the Installation of Sprinkler Systems (hose stream allowance and water supply duration)
  • NFPA 14 - Standard for the Installation of Standpipe and Hose Systems (flow rates and 30-minute supply)
  • NFPA 22 - Standard for Water Tanks for Private Fire Protection (capacity, anti-vortex plate, fill and overflow)
  • NFPA 20 - Standard for the Installation of Stationary Pumps for Fire Protection (suction supply)

Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.