Fire Pump Selection Calculator: Rated Flow, Pressure & Driver Size

Turn a system demand into a fire pump rating. Enter the demand flow, the pressure needed at the most remote outlet, the elevation, friction loss and the suction pressure; the calculator picks the NFPA 20 rated capacity, rounds the rated pressure, checks the churn and 150% curve points, estimates the motor or engine size, and suggests jockey pump and pressure switch settings — in US or metric units.

NFPA 20NFPA 13NFPA 14FM Global DS 3-7

Inputs

1

System demand

Sprinklers + inside hose, or the standpipe demand
100 psi (6.9 bar) for Class I standpipes, 65 psi (4.5 bar) for Class II; the base-of-riser demand pressure for sprinklers
Pump discharge to the highest outlet
Pipe, fittings and valves, from the hydraulic calculation
2

Water supply at pump suction

Residual pressure — tank head, or city main at this flow
No flow — full tank, or city static
3

Selection factors

Safety cushion on the net pressure, commonly 10%
From the pump curve; NFPA 20 allows up to 140%
Typically 60–80% for fire pumps
Brake power peaks beyond the rated point

How to Size a Fire Pump

A fire pump is rated by two numbers: the flow it delivers and the net pressure it adds at that flow. The flow comes from the largest system demand; the pressure is whatever the supply cannot provide on its own.

Net pump pressure = pressure at remote outlet + elevation + friction loss − suction pressure
Elevation = 0.433 psi per ft (0.098 bar per m)
Rated pressure = net pressure + margin, rounded up to the next 5 psi
Rated flow = NFPA 20 standard capacity at or above the demand (demand may be up to 150% of the rating)
Head: 1 psi = 2.31 ft = 0.703 m of water · 1 bar = 10.2 m

The suction pressure is the pressure available at the pump inlet while the demand is flowing — the residual pressure of a city main from a flow test, or the static head of a tank at its lowest level. Using the static (no-flow) pressure of a city main here is the most common way to undersize a pump.

NFPA 20 Rated Fire Pump Capacities

gpmL/mingpmL/mingpmL/min
25954001,5142,0007,570
501894501,7032,5009,462
1003795001,8923,00011,355
1505687502,8393,50013,247
2007571,0003,7854,00015,140
2509461,2504,7314,50017,032
3001,1361,5005,6775,00018,925

Because a listed pump must deliver 150% of its rating, NFPA 20 allows the system demand to be anywhere up to 150% of the rated capacity. Selecting the rating at or just above the demand keeps a reserve for future changes; selecting near 150% gives a smaller, cheaper pump with no reserve. Most designers aim for a demand between 90% and 140% of rated flow.

The Three Points of a Fire Pump Curve

PointFlowNet pressureWhat it controls
Churn (shutoff)0%Not more than 140% of ratedMaximum pressure on pipe, fittings and sprinklers
Rated100%100% of ratedThe nameplate duty
Overload150%Not less than 65% of ratedReserve capacity; the test header flow

Add the highest static suction pressure to the churn pressure to find the greatest pressure the system can see. Where it exceeds 175 psi (12.1 bar) — the rating of standard sprinklers, fittings and valves — the options are a pump with a flatter curve, higher-rated components, a variable speed driver, or zoning. NFPA 20 does not accept a pressure relief valve as the normal means of controlling pressure.

Motor and Engine Power

Water power (hp) = Q × P ÷ 1,714 (Q in gpm, P in psi) · kW = Q × P ÷ 600 (Q in L/min, P in bar)
Brake power = water power ÷ pump efficiency
Driver ≥ the maximum brake power at any flow on the pump curve
Pump ratingWater powerBrake power at 70%Driver with 15% margin
250 gpm @ 100 psi14.6 hp20.8 bhp25 hp (18.5 kW)
500 gpm @ 100 psi29.2 hp41.7 bhp50 hp (37 kW)
750 gpm @ 125 psi54.7 hp78.1 bhp100 hp (75 kW)
1,000 gpm @ 125 psi72.9 hp104.2 bhp125 hp (93 kW)
1,500 gpm @ 150 psi131.3 hp187.5 bhp250 hp (186 kW)
2,000 gpm @ 150 psi175.0 hp250.0 bhp300 hp (224 kW)

Brake power usually peaks between 120% and 150% of rated flow, which is why the calculator adds a driver margin to the rated-point figure; the manufacturer's curve gives the real maximum. Diesel engines are derated 3% for every 1,000 ft (305 m) above 300 ft (91 m) altitude and 1% for every 10 °F (5.6 °C) above 77 °F (25 °C).

Jockey Pump and Pressure Switch Settings

The pressure maintenance (jockey) pump makes up small leaks so the fire pump does not start on a slow pressure drop. NFPA 20 does not fix its size; a flow of about 1% of the fire pump rating — enough to replace the allowable leakage — at a pressure slightly above the fire pump churn pressure is the usual choice. The Annex of NFPA 20 gives the settings the calculator uses:

  • Jockey pump stop = fire pump churn pressure + minimum static suction pressure.
  • Jockey pump start = at least 10 psi (0.7 bar) below the stop point.
  • Fire pump start = 5 psi (0.35 bar) below the jockey start. Additional fire pumps start in 10 psi steps below that.
  • Fire pump stop — manual, at the controller, after the fire is confirmed out. Where automatic stop is permitted, a minimum run timer applies.

Worked Example: 500 gpm Sprinkler and Hose Demand

  1. Demand at the base of the riser: 500 gpm (1,893 L/min) needing 65 psi at the most remote outlet.
  2. Elevation, pump to outlet 40 ft: 0.433 × 40 = 17.3 psi. Friction loss at 500 gpm: 15 psi.
  3. Suction from a tank: 5 psi at the lowest water level.
  4. Net pressure = 65 + 17.3 + 15 − 5 = 92.3 psi; with a 10% margin, 101.6 psi → rated pressure 105 psi (7.2 bar, 74 m head).
  5. Rated flow: the demand equals a standard rating → 500 gpm @ 105 psi.
  6. Water power = 500 × 105 ÷ 1,714 = 30.6 hp; at 70% efficiency 43.8 bhp; with 15% margin 50.3 hp → 60 hp (45 kW) driver.
  7. Churn at 120% = 126 psi; plus 10 psi static suction = 136 psi at the discharge — below 175 psi.
  8. Settings: jockey stop 136 psi, jockey start 126 psi, fire pump start 121 psi.

Friction loss comes from the Fire Hydraulic Calculator, the demand from the Sprinkler Density or Standpipe calculators, and the suction supply from the Fire Water Tank Calculator or a hydrant flow test. For the room itself, see the fire pump room detailed drawing.

Frequently asked questions

How do I calculate the pressure a fire pump must produce?

Add the pressure required at the most remote outlet, the elevation pressure (0.433 psi per foot or 0.098 bar per metre of height) and the friction loss at the demand flow, then subtract the suction pressure available at the pump at that flow. For example 65 + 17.3 + 15 − 5 = 92.3 psi; with a 10% margin and rounding, a 105 psi pump.

What flow ratings do fire pumps come in?

NFPA 20 lists rated capacities of 25, 50, 100, 150, 200, 250, 300, 400, 450, 500, 750, 1,000, 1,250, 1,500, 2,000, 2,500, 3,000, 3,500, 4,000, 4,500 and 5,000 gpm. Pressure ratings are not standardised; each manufacturer offers a range for every capacity.

Can the fire pump rating be smaller than the system demand?

Yes. NFPA 20 permits a pump to supply a demand of up to 150% of its rated capacity, because every listed pump must deliver at least 65% of rated pressure at 150% of rated flow. A 500 gpm demand can therefore be met by a 400 gpm pump if the pressure at that point on the curve is still enough, but there is no reserve for future changes.

What is churn pressure?

Churn, or shutoff, pressure is the pressure the pump develops at zero flow. NFPA 20 limits it to 140% of the rated pressure; real pumps are typically 110–125%. Churn plus the highest static suction pressure is the maximum pressure the system sees and must not exceed the pressure rating of the components.

How do I calculate fire pump motor horsepower?

Water horsepower is gpm × psi ÷ 1,714. Divide by the pump efficiency for brake horsepower. A 500 gpm, 105 psi pump at 70% efficiency needs 500 × 105 ÷ 1,714 ÷ 0.70 = 43.8 bhp at the rated point. The driver must cover the highest brake power anywhere on the curve, which is usually 10–20% more, so a 60 hp motor would be selected.

How big should the jockey pump be?

NFPA 20 does not give a size. A common rule is about 1% of the fire pump rated flow — 5 gpm for a 500 gpm pump — which is enough to make up the allowable leakage, at a discharge pressure equal to the fire pump churn pressure plus the static suction pressure. It should not be large enough to supply a single sprinkler, or the fire pump would never start.

What pressure should the fire pump start at?

Following the NFPA 20 Annex: set the jockey pump to stop at the fire pump churn pressure plus the minimum static suction pressure, to start 10 psi below that, and set the fire pump to start 5 psi below the jockey start. With a churn pressure of 126 psi and 10 psi suction that is 136, 126 and 121 psi.

References & standards

  • NFPA 20 - Standard for the Installation of Stationary Pumps for Fire Protection (rated capacities, 140% churn and 65% at 150% curve limits, driver sizing, pressure maintenance pumps, pressure switch settings in Annex A)
  • NFPA 13 - Standard for the Installation of Sprinkler Systems (system demand)
  • NFPA 14 - Standard for the Installation of Standpipe and Hose Systems (flow and residual pressure)
  • FM Global Property Loss Prevention Data Sheet 3-7 - Fire Protection Pumps

Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.