✨ Free Online Ductulator

Online Ductulator — Round & Rectangular Duct Sizer

A free online ductulator for round and rectangular ductwork. Size by friction rate or velocity, in imperial or metric, with standard duct sizes, air density correction and a rectangular-to-round converter. Results update as you type. Also known as a ductulador online (Spanish).

📐 Ductulator

Sets the velocity limits used for the check below
Duct material
Air density correction — altitude & duct air temperature
ft
°F

Standard air is 0 ft and 70°F (21°C), density 0.075 lb/ft³ (1.2 kg/m³). Enter the temperature of the air inside the duct, not the outdoor temperature. Examples: at 2,000 ft (610 m), cooled supply air at 55°F (13°C) is about 4% below standard density and hot exhaust air at 113°F (45°C) about 14% below; at 5,000 ft (1,520 m), standard-temperature air is about 17% below. Friction loss scales with density; velocity does not.

Size by
in.wg / 100 ft
ft
Straight duct + equivalent length of all fittings — used for total pressure drop
I want to enter
Duct shape

🔄 Rectangular → Round

in
in
Equivalent round —

🔄 Round → Rectangular

in
in
Second side — Rounded up to the next standard increment

📊 Ductulator Chart — CFM to Duct Size

This duct size chart is generated from the same equations the calculator above uses, for galvanised metal duct at standard air. Each cell shows the exact calculated diameter, with the recommended standard round size in brackets. Round duct steps in 1 in increments to 12 in and 2 in increments above, so odd sizes such as 13, 15, 17 and 19 in are not shown. The velocity column is at the exact calculated diameter. Need it on paper? Download the duct size chart PDF.

Airflow (CFM)Airflow (L/s) 0.05 in.wg/100ft
0.41 Pa/m — quiet
0.08 in.wg/100ft
0.65 Pa/m
0.10 in.wg/100ft
0.82 Pa/m — standard
Velocity at 0.10
100476.7" (7")6.1" (7")5.9" (6")535 fpm / 2.7 m/s
200948.7" (9")7.9" (8")7.6" (8")636 fpm / 3.2 m/s
30014210.2" (11")9.2" (10")8.8" (9")703 fpm / 3.6 m/s
40018911.3" (12")10.3" (11")9.9" (10")754 fpm / 3.8 m/s
60028313.2" (14")12.0" (12")11.5" (12")834 fpm / 4.2 m/s
80037814.7" (16")13.4" (14")12.8" (14")895 fpm / 4.6 m/s
1,00047216.0" (16")14.6" (16")13.9" (14")946 fpm / 4.8 m/s
1,20056617.1" (18")15.6" (16")14.9" (16")990 fpm / 5.0 m/s
1,60075519.1" (20")17.4" (18")16.6" (18")1,063 fpm / 5.4 m/s
2,00094420.7" (22")18.9" (20")18.1" (20")1,123 fpm / 5.7 m/s
2,5001,18022.5" (24")20.5" (22")19.7" (20")1,186 fpm / 6.0 m/s
3,0001,41624.2" (26")22.0" (22")21.1" (22")1,241 fpm / 6.3 m/s
4,0001,88826.9" (28")24.5" (26")23.5" (24")1,333 fpm / 6.8 m/s
5,0002,36029.3" (30")26.7" (28")25.5" (26")1,408 fpm / 7.2 m/s
6,0002,83231.4" (32")28.6" (30")27.3" (28")1,473 fpm / 7.5 m/s
8,0003,77634.9" (36")31.8" (32")30.5" (32")1,582 fpm / 8.0 m/s
10,0004,71938.0" (38")34.6" (36")33.1" (34")1,671 fpm / 8.5 m/s

For duct board multiply the round diameter by about 1.06, and for fully stretched flexible duct by about 1.12, at the same airflow and friction rate. The calculator applies this automatically when you change duct material.

ℹ️ How to Use This Ductulator

  1. Pick your units and application. The application setting only controls the velocity check — it does not change the sizing maths.
  2. Pick the duct material. Metal is smoothest; duct board and flex need a larger duct for the same friction rate.
  3. Open air density correction if the project is at altitude or the duct carries hot or cold air. Enter the air temperature inside the duct. Leave it at 0 ft / 70°F for standard conditions.
  4. Choose the sizing method. Friction rate is the normal method for a full system so pressure drop stays consistent across every branch. Velocity is used where noise or a fixed duct route governs.
  5. Enter total equivalent length — straight duct plus the equivalent length of every elbow, tee and transition on the index run. This gives the total pressure drop the fan has to overcome.
  6. Enter airflow to get a size, or a size to get airflow. For rectangular duct, fix the side your ceiling void allows and the tool solves the other side on standard increments.
  7. Compare the two standard sizes. The exact calculated diameter almost never lands on a stocked size, so the tool shows the standard size either side with its real velocity and friction, and flags the smaller one when it stays within 2% of your target. Rounding up automatically is not always right — one step up in round duct can drop the friction 40% or more below design.
  8. Check the warnings below the results for velocity limits and aspect ratio before you commit the size to a drawing.

Rectangular sizing uses the Huebscher equivalent diameter for friction, but velocity is always calculated from the real rectangular area — the two are not the same number.

Prefer a walkthrough with screenshots? Follow the step-by-step online duct sizing tutorial on MEPBase.

📖 Duct Sizing Guide — Velocities, Friction Rates & FAQ

What is a ductulator?

A ductulator is the classic HVAC duct sizing calculator — traditionally a rotating cardboard wheel, made familiar by the Trane and McQuay versions, that engineers spin to line up airflow, friction rate, velocity and duct size. This online ductulator does exactly the same job digitally: enter CFM or L/s with your design friction rate or velocity and get the round diameter or rectangular equivalent instantly. No wheel, nothing to install, and it works in a phone browser on site.

You will see the tool spelled ductilator, ductalator or duct-u-lator in searches and on site. They all mean the same thing — ductulator is the correct spelling, and every version refers to the same duct sizing tool for air distribution.

How the calculation works

Duct friction loss follows the Darcy-Weisbach equation with the Colebrook friction factor. For galvanised duct carrying standard air, ASHRAE gives a well-known power-law fit, which this calculator uses with a small size-dependent calibration:

Δp per 100 ft = 0.109 × Q1.9 / D5.02 Q = airflow (CFM) D = round diameter (in) Δp = friction loss (in.wg per 100 ft) Equivalent diameter (Huebscher, rectangular duct): De = 1.30 × (a × b)0.625 / (a + b)0.25 Air density correction: ρ / ρ_std = (1 − 6.8754×10⁻⁶ × z)5.2559 × 530 / (T + 460) z = elevation (ft) T = air temperature in the duct (°F) Δp_actual = Δp_standard × (ρ / ρ_std)

Checked against a full Darcy-Weisbach / Colebrook solution, results fall within about 2% across 100–10,000 CFM and sit slightly on the conservative (larger duct) side — the same basis as the traditional ductulator wheels.

Because friction varies with diameter to the power of 5.02, a small size change has a large effect. Going from a 12" to a 14" duct at the same airflow cuts the friction loss to roughly half (800 CFM: 0.139 → 0.064 in.wg/100 ft).

For when to use each method on a real project, read equal friction vs velocity method for duct sizing.

Recommended duct velocities

ApplicationMain ductsBranch ducts
Residences700–900 fpm (3.5–4.5 m/s)600 fpm (3 m/s)
Offices, hotels, hospitals1,200–1,600 fpm (6–8 m/s)800–1,200 fpm (4–6 m/s)
Shops, cafeterias, commercial1,500–1,800 fpm (7.5–9 m/s)1,000–1,300 fpm (5–6.5 m/s)
Industrial1,800–2,500 fpm (9–12.5 m/s)1,200–1,800 fpm (6–9 m/s)
Return / exhaust ducts600–1,000 fpm (3–5 m/s)600–800 fpm (3–4 m/s)

Noise-critical spaces — bedrooms, studios, conference rooms, places of worship — should stay at the lower end of each range.

Typical design friction rates

Duct systemFriction rate (imperial)Head loss (metric)
Supply ducts — comfort HVAC0.08–0.10 in.wg/100ft0.65–0.85 Pa/m
Return ducts0.05–0.08 in.wg/100ft0.4–0.65 Pa/m
Exhaust ducts0.08–0.10 in.wg/100ft0.65–0.85 Pa/m
Low-noise / low-energy design0.05–0.08 in.wg/100ft0.4–0.65 Pa/m

The industry default of 0.1 in.wg per 100 ft (about 0.82 Pa/m) balances duct size against fan energy for most comfort applications, and it is this tool's default. The total pressure drop result feeds straight into fan selection — take it to the fan static pressure calculator.

Duct aspect ratio

SMACNA recommends keeping rectangular duct aspect ratio at or below 4:1. A tall narrow duct carries the same air as a squarer one but needs more sheet metal, more insulation, more hangers and produces more friction than the equivalent diameter suggests. Where a ceiling void forces a high ratio, split the run into two parallel ducts instead of pushing past 4:1.

Frequently asked questions

What is a ductulator?
A duct sizing calculator — traditionally a rotating wheel — that matches airflow, friction rate, velocity and duct size. This page is a free online version supporting round and rectangular duct in both unit systems.
Is it spelled ductulator, ductilator or ductalator?
Ductulator is correct. Ductilator, ductalator and duct-u-lator are common misspellings of the same HVAC tool, so if you searched any of those, this calculator is what you were looking for.
What size duct do I need for 800 CFM?
At the standard 0.1 in.wg/100ft friction rate, 800 CFM needs a 12.8" round metal duct. Round duct steps in 2 in increments above 12 in, so the two real options are 12" (friction 0.139, 39% over target) and 14" (friction 0.064, comfortably under). Specify 14" — 12" would be undersized. A rectangular equivalent is 10 × 14".
What friction rate should I use for duct sizing?
0.08–0.10 in.wg/100ft (0.65–0.85 Pa/m) for supply and 0.05–0.08 for return in typical comfort applications. Lower friction gives bigger, quieter ducts; higher friction gives smaller ducts but more fan energy and more noise.
What is the maximum velocity for HVAC ducts?
Residential mains 700–900 fpm, commercial mains 1,200–1,800 fpm, branches 600–1,300 fpm, returns 600–1,000 fpm. Keep noise-sensitive spaces at the low end.
How do you convert rectangular duct to round?
With the Huebscher equivalent diameter: De = 1.30 × (a×b)0.625 / (a+b)0.25, which gives the round size with equal friction loss at the same airflow. The converters above do it both ways and round to standard sizes.
Does altitude or air temperature change duct sizing?
Yes. Friction loss is proportional to the density of the air inside the duct, so use the duct air temperature, not the outdoor temperature. At 2,000 ft (610 m), cooled supply air at 55°F (13°C) is only about 4% below standard density, while hot exhaust air at 113°F (45°C) is about 14% below. At 5,000 ft (1,520 m), standard-temperature air is about 17% below. Velocity is unaffected because it depends only on volumetric flow and area. Open the air density panel in the calculator to apply it.
Why do the imperial and metric answers differ slightly?
Because the two standard size series are different, not because the maths differs. Imperial round duct runs 4–12" in 1" steps then 2" steps; metric follows the EN 1506 series (250, 300, 315, 355, 400, 450, 500 mm and so on). The calculated diameter is identical in both — 18.0 in is 457 mm — but the nearest stocked size above it is 20 in (508 mm) in one series and 500 mm in the other. Size in whichever series your supplier actually stocks.
Is there a ductulator app?
You do not need one. This ductulator runs in any phone or desktop browser with nothing to install, and every calculation happens on your device. Use your browser's Add to Home screen option to open it like an app. An internet connection is needed to load the page.
Is this a ductulador online (Spanish)?
Yes. Ductulador is the Spanish name for the same duct sizing tool, and this calculator works the same way in metric units: enter the airflow in L/s or m³/h and a friction rate in Pa/m to get the round or rectangular duct size. Es un ductulador online gratuito: calcula el tamaño de ductos redondos y rectangulares por pérdida de fricción o velocidad.

Related HVAC tools

Guides and downloads on MEPBase

References

  • ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design
  • SMACNA HVAC Systems Duct Design
  • SMACNA HVAC Duct Construction Standards — Metal and Flexible
  • EN 1506 — Ventilation for buildings: circular sheet metal ducts, dimensions

Last updated: 27 September 2026

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.