Pick the occupancy hazard and get the NFPA 13 design density and area, the number of sprinklers operating, the flow and pressure each one needs, and the total water demand with hose stream and duration. Area adjustments for dry pipe systems, sloped ceilings and quick-response sprinklers are built in, and every value works in US or metric units.
NFPA 13 sizes a sprinkler system for a fire in the hydraulically most demanding part of the building — the design area (also called the remote area or area of operation). Every sprinkler inside that area must deliver at least the design density, the flow per unit of floor area, at the same time. Multiplying the two gives the minimum sprinkler demand, and the hose stream allowance is added for fire-fighter hose lines.
Because the number of sprinklers is rounded up to a whole head, the real flow is usually N × q rather than exactly density × area; the calculator reports both and uses the larger. A density of 1 gpm/ft² equals 40.75 mm/min (L/min per m²).
| Hazard | Density | Design area | Sprinkler demand | Hose stream | Duration | Max. coverage / sprinkler |
|---|---|---|---|---|---|---|
| Light | 0.10 gpm/ft² (4.1 mm/min) | 1,500 ft² (139 m²) | 150 gpm (568 L/min) | 100 gpm | 30 min | 225 ft² (20.9 m²) |
| Ordinary Group 1 | 0.15 gpm/ft² (6.1 mm/min) | 1,500 ft² (139 m²) | 225 gpm (852 L/min) | 250 gpm | 60–90 min | 130 ft² (12.1 m²) |
| Ordinary Group 2 | 0.20 gpm/ft² (8.1 mm/min) | 1,500 ft² (139 m²) | 300 gpm (1,136 L/min) | 250 gpm | 60–90 min | 130 ft² (12.1 m²) |
| Extra Group 1 | 0.30 gpm/ft² (12.2 mm/min) | 2,500 ft² (232 m²) | 750 gpm (2,839 L/min) | 500 gpm | 90–120 min | 100 ft² (9.3 m²) |
| Extra Group 2 | 0.40 gpm/ft² (16.3 mm/min) | 2,500 ft² (232 m²) | 1,000 gpm (3,785 L/min) | 500 gpm | 90–120 min | 100 ft² (9.3 m²) |
These are the single density/area points used by current editions of NFPA 13 for new systems; earlier editions offered a curve, allowing a lower density over a larger area. The shorter duration applies where waterflow and supervisory devices are electrically supervised and monitored at a constantly attended location. Hose stream is the total of inside and outside hose. Extra hazard sprinklers may cover 130 ft² (12.1 m²) where the density is below 0.25 gpm/ft².
| Classification | Fuel load and heat release | Typical occupancies |
|---|---|---|
| Light Hazard | Low quantity and combustibility of contents | Offices, schools, hospitals, hotels and apartments, churches, museums, restaurant seating areas |
| Ordinary Hazard Group 1 | Moderate quantity, low combustibility, stock up to 8 ft (2.4 m) | Parking garages, restaurant kitchens, laundries, bakeries, electronics plants, canneries |
| Ordinary Hazard Group 2 | Moderate to high quantity and combustibility, stock up to 12 ft (3.7 m) | Retail and mercantile, machine shops, repair garages, library stack rooms, textile and wood product assembly |
| Extra Hazard Group 1 | Very high combustibility, dust or lint, little or no flammable liquid | Sawmills, plywood and particle board plants, printing with low flash point inks, plastic foam upholstery, die casting |
| Extra Hazard Group 2 | Moderate to substantial flammable or combustible liquids, or extensive shielding | Flammable liquid spraying, flow coating, plastics processing, solvent cleaning, varnish and paint dipping |
Classification follows the fuel load of the space, not the name of the building: a hospital is light hazard, but its kitchen and laundry are ordinary hazard. Storage above the heights shown, rack storage and plastics storage are designed to the storage chapters of NFPA 13, not to this table.
Where more than one adjustment applies they are compounded — a dry system under a steep roof uses 1,500 × 1.3 × 1.3 = 2,535 ft². The design area is laid out as a rectangle with its long side, at least 1.2 × √A, parallel to the branch lines.
Carry the flow per sprinkler into the Sprinkler K-Factor Calculator, check the layout with the Sprinkler Spacing Calculator, find pipe losses with the Fire Hydraulic Calculator and size storage with the Fire Water Tank Calculator. The full method is explained in the Fire Fighting System Design Calculation guide.
Design density is the minimum flow of water each unit of floor area must receive from the sprinklers, in gpm/ft² or mm/min (L/min per m²). NFPA 13 sets it by occupancy hazard: 0.10 gpm/ft² for light hazard, 0.15 and 0.20 for ordinary hazard Groups 1 and 2, and 0.30 and 0.40 for extra hazard Groups 1 and 2.
Multiply the design density by the design area to get the sprinkler demand, then add the hose stream allowance. For ordinary hazard Group 2: 0.20 gpm/ft² × 1,500 ft² = 300 gpm, plus 250 gpm hose = 550 gpm as the code minimum. A hydraulic calculation of the actual pipework usually gives 10–20% more because sprinklers nearer the supply discharge above the minimum.
It is the hydraulically most remote area of sprinklers assumed to operate in a fire: 1,500 ft² (139 m²) for light and ordinary hazard and 2,500 ft² (232 m²) for extra hazard. It is increased 30% for dry pipe systems and for ceilings sloped more than 2 in 12, and may be reduced 25–40% for quick-response sprinklers in wet systems.
Divide the design area by the coverage area per sprinkler and round up. With 1,500 ft² and 130 ft² per sprinkler that is 11.5, so 12 sprinklers. Along each branch line the number is 1.2 × √A divided by the sprinkler spacing, rounded up.
NFPA 13 requires at least 7 psi (0.5 bar) at any operating sprinkler. The pressure needed for the design flow is P = (q ÷ K)², so a K5.6 sprinkler delivering 26 gpm needs 21.6 psi. If the result is below 7 psi, 7 psi governs and the sprinkler discharges more than the minimum flow.
Multiply by 40.75. A density of 0.15 gpm/ft² is 6.1 mm/min, which is the same as 6.1 L/min per square metre. To convert the other way, divide mm/min by 40.75.
NFPA 13 requires 30 minutes for light hazard, 60–90 minutes for ordinary hazard and 90–120 minutes for extra hazard. The lower figure is permitted where waterflow alarm and supervisory devices are electrically supervised and monitored at a constantly attended location.
Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.