Fire Alarm Battery Calculator 🔋

Size fire alarm control panel (FACP) standby batteries per NFPA 72 — enter device standby & alarm currents, apply the 24hr + 5min requirement and 20% derating, and get the standard battery size in Ah.

📊 Battery Load Worksheet

Device Currents (from datasheets)
DeviceQtyStandby mAAlarm mA
Fire Alarm Control Panel
Smoke / Heat Detectors
Manual Call Points
Monitor / Control Modules
Sounders / Horn-Strobes
Beacons / Strobes
Other Devices (repeater, etc.)
Defaults are typical values — always replace with actual datasheet currents for final design. For addressable systems, notification appliance currents may be on separate NAC/booster power supplies (calculate those batteries separately).
NFPA 72 Requirements
NFPA 72: 24 hrs (60 for some codes)
5 min · 15 min for voice evac
NFPA 72 practice: 20% (×1.20)

📊 Battery Sizing Results

🔋

Enter device currents and click Calculate

Typical DeviceStandbyAlarm
Addressable panel (1 loop)120–250 mA250–500 mA
Addressable smoke detector0.2–0.4 mA0.5–2 mA
Manual call point0.2–0.4 mA0.5–2 mA
Monitor / control module0.3–0.5 mA2–10 mA
Horn-strobe (24V)0 mA60–180 mA
Wall strobe 15–75 cd0 mA60–160 mA
Indicative ranges — always use the manufacturer's datasheet values

How to Calculate Fire Alarm Battery Size (NFPA 72 Method)

Every fire alarm control panel needs a secondary power supply — batteries that keep the system alive when mains power fails. NFPA 72 defines exactly how much: the batteries must run the system in normal standby for 24 hours and, at the end of that period, still operate every notification appliance in full alarm for 5 minutes (15 minutes for emergency voice/alarm communication systems). Undersize the batteries and the installation fails inspection; oversize them and they may not fit the panel cabinet or exceed the charger's capability.

The NFPA 72 Battery Formula

Standby Ah = Istandby (A) × 24 hrs
Alarm Ah   = Ialarm (A) × (5 ÷ 60) hr
Required Ah = (Standby Ah + Alarm Ah) × 1.20

Where Istandby is the sum of all device quiescent currents (panel + detectors + call points + modules), and Ialarm is the sum of all device alarm currents including every sounder and strobe. The 1.20 factor is the 20% derating applied in NFPA 72 practice to cover battery aging and temperature — the system must still meet the requirement near the battery's end of life.

Worked Example: Addressable System, 120 Detectors

Panel (150/300 mA), 120 smoke detectors (0.3/1 mA), 20 call points (0.3/1 mA), 8 modules (0.4/5 mA), 40 horn-strobes (0/80 mA), standard 24 hr + 5 min, 20% derating:

Notice the pattern: standby dominates the calculation — 24 hours of quiescent load is almost always far larger than 5 minutes of alarm load, which is why cutting standby current (fewer LEDs, efficient devices) shrinks batteries more than anything else.

Design Tips

Frequently Asked Questions

How do you calculate fire alarm battery size?
Ah = (standby current × 24 hr) + (alarm current × 5/60 hr), all × 1.20 derating — then pick the next standard battery size. This tool automates the full NFPA 72 worksheet.
Why 24 hours + 5 minutes?
NFPA 72's secondary power requirement: survive a 24-hour mains outage and still sound a full alarm for 5 minutes at the end of it (15 min for voice evacuation systems).
What is the 20% derating factor?
A ×1.20 multiplier covering battery capacity loss from aging and temperature — so the system still complies near the battery's end of service life.
Why 2 × 12V batteries?
Fire alarm panels run at 24V DC — two 12V SLA batteries in series give 24V at the same Ah rating (2 × 12V 18Ah = 24V 18Ah).
How often should the batteries be replaced?
Typically every 3–5 years, or immediately when the annual load test shows capacity below the calculated requirement.

Disclaimer: This tool provides preliminary sizing using typical device currents. Battery calculations submitted for authority approval must use exact manufacturer datasheet values and comply with the applicable edition of NFPA 72 / local codes.

📚 References