UPS Sizing Calculator ⚡

Size a UPS in two steps — kVA rating from load, power factor, growth and loading margins, and battery bank (Wh, Ah, 12V blocks) from the required backup runtime. For server rooms, NVRs, BMS panels and ELV head-end equipment.

📊 Load & Requirements

Connected Load
Sum of nameplate ratings of all equipment on the UPS
IT loads 0.9–1.0 · mixed 0.8
Typical 20–30%
UPS Sizing
Design practice: 75–80%
5–15 min with generator · 30–60+ without
Battery Bank
VRLA typ. 80%
IEEE practice: 25%
From UPS datasheet (24–480V)

📊 UPS & Battery Results

Enter load data and click Calculate

Typical LoadLoadUPS @ 15 min*
BMS / ELV panel0.5 kW1 kVA
NVR + switches rack1.5 kW3 kVA
Small server room5 kW10 kVA
Server room8 kW15 kVA
Data hall row20 kW40 kVA
*at 0.9 PF, 25% growth, 80% loading — indicative

How to Size a UPS (kVA + Battery)

UPS sizing has two independent halves that engineers often mix up: the power rating (kVA/kW) — can the UPS carry the load — and the battery bank — for how long. A 10 kVA UPS can have 5 minutes or 2 hours of runtime depending entirely on the batteries behind it. This calculator solves both, the way a consultant's sizing sheet does.

Step 1 — UPS kVA Rating

Load VA = Load W ÷ Power Factor
Design VA = Load VA × (1 + Growth %)
Required kVA = Design VA ÷ Max Loading %  →  next standard rating

Two margins matter: growth (20–30% — loads always increase over the UPS's 10-year life) and loading (design at 75–80% of the rating, never 100% — headroom for inrush, load steps and reliability). Also check the UPS's kW rating: modern units are rated at 0.9–1.0 output PF, and the load must not exceed kVA or kW, whichever comes first.

Step 2 — Battery Bank

Battery Wh = Load W × (Runtime ÷ 60) ÷ ηinverter ÷ DoD × (1 + Aging %)
String Ah = Wh ÷ VDC  ·  Blocks = VDC ÷ 12

The 25% aging margin follows IEEE battery-sizing practice — the bank must still deliver the runtime near end of life. Important: the energy method is preliminary; at short runtimes (5–15 min) batteries discharge at high rates where usable capacity drops (Peukert effect), so final selection must use the manufacturer's constant-power runtime charts.

Worked Example: 8 kW Server Room

Design Tips

Frequently Asked Questions

How do you calculate UPS size?
Load VA (= W ÷ PF) × (1 + growth) ÷ max loading → next standard kVA. Example: 8 kW @ 0.9 PF, +25%, @80% → 13.9 → 15 kVA.
kVA vs kW — what's the difference?
kVA is apparent power, kW = kVA × PF is real power. A UPS has both ratings; your load must fit within both.
How is battery backup time calculated?
Wh = W × hours ÷ inverter efficiency ÷ DoD × aging factor; Ah = Wh ÷ DC voltage. Verify short runtimes against vendor constant-power charts.
Why load a UPS to only 80%?
Headroom for inrush and load growth, longer battery runtime, less inverter stress — 75–80% is standard design practice.
What runtime should I choose?
5–15 min with a generator (transfer ride-through); 30–60+ min without one, or enough for graceful server shutdown.

Disclaimer: Preliminary sizing only. Final UPS and battery selection must be verified against manufacturer kW/kVA ratings, constant-power runtime charts and site conditions.

📚 References