BMS Points List Calculator 🎛️

Generate a BMS IO points summary from your equipment schedule — DI, DO, AI & AO totals with equipment breakdown, spare capacity and an indicative DDC controller count. Per ASHRAE Guideline 13 & BACnet practice.

📊 Equipment IO Worksheet

Equipment Quantities & Points per Unit
EquipmentQtyDIDOAIAO
AHU (VFD, hardwired)
FCU
Chiller (hardwired pts)
Pump — VFD
Pump — DOL
Cooling Tower
Exhaust / Supply Fan
Water Tank (level)
Other / Custom
Defaults are typical hardwired points per unit — edit to match your control philosophy. Networked FCU/VAV controllers with own IO count as integrated (set points to 0 and use soft points below).
System Settings
ASHRAE G13 practice: 10–25%
Typical controllers: 32–128 IO
BACnet/Modbus points (chillers, meters)

📊 Points Summary

🎛️

Enter equipment quantities and click Generate

What is a BMS Points List (IO Schedule)?

The points list is the single most important document in BMS design — the master schedule of every input and output the system monitors and controls, listed equipment by equipment. It drives everything downstream: DDC controller selection, panel sizing, cable and containment schedules, graphics count, software licensing and — most visibly — the system price. BMS vendors quote per point, so an inflated or missing points list flows straight into commercial disputes at tender stage.

DI, DO, AI, AO — the Four Point Types

How the Calculation Works

Points per type = Σ (Equipment Qty × Points per Unit)
Hard Total = DI + DO + AI + AO
With Spare = Hard Total × (1 + Spare %)   [ASHRAE G13: 10–25%]
DDC Count ≈ With Spare ÷ IO per Controller (budget estimate)

The per-unit defaults in this tool reflect common hardwired control philosophies — a VFD AHU at ~17 points, a DOL pump at 4, an FCU at 4. Every value is editable because the sequence of operations decides the points: add a return-air humidity sensor and the AHU gains an AI; move FCUs to networked thermostats and their hard points drop to zero (they become soft points instead).

Worked Example: Mid-Size Commercial Building

4 AHUs, 60 FCUs, 2 chillers (hardwired safeties), 4 VFD pumps, 2 cooling towers, 10 fans, 2 tanks — with 20% spare and 64-point DDCs:

Design Tips

Frequently Asked Questions

What is a BMS points list?
The master IO schedule of every DI/DO/AI/AO the BMS handles, per equipment — it drives controller selection, panel design, cabling and pricing.
What's the difference between DI, DO, AI and AO?
DI reads on/off (status, trip); DO commands on/off (start/stop); AI reads variables (temp, pressure); AO commands variables (valve, VFD speed).
How much spare capacity should I include?
10–25% per ASHRAE Guideline 13 practice — 20% is the most common specification value, ideally applied per point type per controller.
How many points does an AHU need?
A typical VFD AHU runs 15–20 hard points (status/trip DIs, start DO, temps + filter ΔP AIs, valve/damper/speed AOs) — the exact count follows the sequence of operations.
What are soft points?
Points read over BACnet/Modbus integration (chillers, meters, VFDs) instead of hardwired IO — no terminals used, but they count for licensing and engineering.

Disclaimer: Point counts are indicative for budgeting and tender-stage design. The final points list must follow the project's approved sequence of operations and specifications.

📚 References