Cable Size Calculator ⚡

Size copper or aluminium cables in mm² (IEC 60364 / BS 7671) or AWG / kcmil (NEC Table 310.16) by current-carrying capacity and voltage drop, with temperature and grouping derating and breaker coordination (Ib ≤ In ≤ Iz).

Ib ≤ In ≤ Iz  and  VD = k × I × L × (R cos φ + X sin φ) ≤ limit
k = 2 for single phase, √3 for three phase  ·  the larger cable from the two checks governs

📊 Input Parameters

Leave empty to skip the voltage-drop check. 1 ft = 0.3048 m

📊 Results

⚡

Enter the load current and click Calculate

Complete Guide to Electrical Cable Sizing

Choosing the right cable size is one of the most important decisions in any electrical installation. Get it wrong and you risk overheating, nuisance tripping, equipment malfunction, energy waste, or fire. This guide explains how engineers size cables and how this calculator applies those rules under IEC, BS 7671 and NEC.

Cable Size for Common Breaker Ratings (Quick Chart)

Smallest single-core cable whose current-carrying capacity covers the breaker rating, reference method C (clipped direct), 30°C ambient, one circuit, no voltage-drop allowance. Use the calculator above for your real conditions.

Breaker (A)Copper PVC (mm²)Copper XLPE (mm²)Aluminium XLPE (mm²)
6 A1.51.516
10 A1.51.516
16 A1.51.516
20 A2.51.516
25 A42.516
32 A4416
40 A6416
50 A10616
63 A161016
80 A251625
100 A251625
125 A352535
160 A703570
200 A957070
250 A12070120

The Two Tests Every Cable Must Pass

A conductor is only correctly sized when it satisfies both of the following. The larger of the two results is the size you install.

1. Current-carrying capacity (ampacity). The cable must carry the current without exceeding its insulation temperature. The tabulated ampacity is reduced by derating factors, and the result (Iz) must be at least the rating of the protective device (In).

2. Voltage drop. Resistance and reactance cause the voltage to fall along the run. Excessive drop dims lighting, weakens motor torque and trips controls. Limits are typically 3% for final circuits and 5% overall.

Breaker Coordination: Ib ≤ In ≤ Iz

If Iz falls below In, the breaker could allow current the cable cannot handle, letting it overheat before the device trips. The calculator selects the breaker first, then the smallest standard cable whose derated ampacity clears it.

Derating (Correction) Factors

Temperature: hotter surroundings reduce how much heat the cable can shed. Factors come from IEC 60364-5-52 Table B.52.14 and NEC Table 310.15(B)(1).

Grouping / bunching: cables packed together in a conduit or tray warm each other. Factors come from IEC Table B.52.17 and NEC Table 310.15(C)(1) (more than three current-carrying conductors).

Installation method and insulation: XLPE (90°C) carries more current than PVC (70°C) for the same size, and clipped-direct runs carry more than cables enclosed in thermal insulation.

Cable Sizing in the UK, US and Australia

NEC Wire Size Chart (Copper, Table 310.16)

Allowable ampacities for not more than three current-carrying copper conductors at 30°C ambient. Small conductor overcurrent limits of 240.4(D) still apply.

Size≈ mm²60°C (A)75°C (A)90°C (A)
14 AWG2.08152025
12 AWG3.31202530
10 AWG5.26303540
8 AWG8.37405055
6 AWG13.3556575
4 AWG21.2708595
3 AWG26.785100115
2 AWG33.695115130
1 AWG42.4110130145
1/0 AWG53.5125150170
2/0 AWG67.4145175195
3/0 AWG85165200225
4/0 AWG107.2195230260
250 kcmil126.7215255290
300 kcmil152240285320
350 kcmil177.3260310350
400 kcmil202.7280335380
500 kcmil253.4320380430
600 kcmil304350420475

Voltage Drop Formula Used

Single phase:  VD = 2 × I × L × (R·cosφ + X·sinφ)
Three phase:   VD = √3 × I × L × (R·cosφ + X·sinφ)

R = ρ ÷ A  (Ω/m),  ρCu ≈ 0.0225,  ρAl ≈ 0.036 Ω·mm²/m  (at operating temp)
X ≈ 0.00008 Ω/m,  A = cross-section (mm²),  L = one-way length (m)

VD% = (VD ÷ system voltage) × 100. For a dedicated voltage-drop check, use the Voltage Drop Calculator.

Copper vs Aluminium

Copper conducts better, so for a given current it needs a smaller cross-section and produces less voltage drop, which suits final circuits and tight routes. Aluminium is lighter and cheaper per amp, which makes it popular for large feeders and risers, but it typically needs one to two sizes larger and careful terminations.

IEC / BS 7671 Cable Sizes and Ampacities

Reference values used by this tool (single-core cables, reference method C, copper, 30°C, single circuit):

Size (mm²)≈ AWG / kcmilPVC (A)XLPE (A)Typical use
1.51617.523Lighting circuits
2.5142431General socket outlets
4123242Heavy appliances
6104154Sub-circuits, AC units
1085775Cookers, large motors
16676100Sub-mains / feeders
254101133Distribution feeders
352125164Feeders
501/0151198Main feeders
702/0192253Sub-mains
953/0232306Risers
120250 kcmil269354Risers / incomers
150300 kcmil309407Main incomers
185350 kcmil353464Main incomers
240500 kcmil415546Transformer / main runs

Reference figures for guidance. Actual ampacity depends on the installation method, cable construction and local code — always verify against the manufacturer's data and applicable regulations.

Worked Example

A 3-phase 415 V motor draws 50 A, fed by a 60 m copper PVC cable, 40°C ambient, with three other circuits bunched (4 in total), 3% drop allowed, PF 0.85:

Enter these values above to see the full result and which criterion governs. To start from kW instead of amps, use the kW to Cable Size Calculator.

Common Mistakes to Avoid

Frequently Asked Questions

How do I calculate the correct cable size?

A cable must pass two checks. First, its current-carrying capacity after derating (Iz) must be at least the protective device rating (In), which in turn is at least the design current (Ib): Ib ≤ In ≤ Iz. Second, the voltage drop over the run must stay within the limit, typically 3% for final circuits and 5% overall. The larger cable from the two checks governs. This calculator does both.

What size cable do I need for a 32 A or 63 A breaker?

For copper single-core PVC cable clipped direct (reference method C) at 30°C with no grouping, a 32 A breaker needs 4 mm² and a 63 A breaker needs 16 mm². Higher ambient temperature, grouping or a long run will increase the size, so enter your actual conditions in the calculator.

What is current carrying capacity?

Current carrying capacity (ampacity) is the maximum continuous current a conductor can carry without exceeding its insulation temperature: 70°C for PVC and 90°C for XLPE. Tabulated values assume about 30°C ambient and one circuit, so they are multiplied by temperature and grouping factors for real installations.

What is the maximum allowable voltage drop?

A common rule is 3% for lighting and final circuits and up to 5% from the origin of the installation to the load. BS 7671 Appendix 4 uses 3% for lighting and 5% for other uses on a public supply, and the NEC informational notes recommend 3% on a branch circuit and 5% total. Confirm the limit in your local code or project specification.

How is cable sizing different in the UK, US and Australia?

The UK uses BS 7671 Appendix 4 tables, which follow the IEC method used in this calculator. The US uses NEC Table 310.16 in AWG and kcmil, which this calculator covers in its NEC mode, with ambient correction, the adjustment for more than three current-carrying conductors and the 240.4(D) small conductor limits. Australia uses AS/NZS 3008.1.1, which assumes a 40°C ambient air temperature, so select 40°C here for an estimate and verify against AS/NZS 3008 tables.

Should I use copper or aluminium cable?

Copper has higher conductivity, so for the same current it needs a smaller cross-section and gives lower voltage drop. Aluminium is lighter and cheaper but needs roughly one to two sizes larger for the same ampacity. Aluminium is common for large feeders; copper dominates final circuits.

What is a derating (correction) factor?

Tabulated ampacities assume ideal conditions (about 30°C ambient, one circuit). When the ambient is hotter or several cables are bunched together, the safe current is reduced by multiplying by temperature and grouping factors. The derated ampacity is what must exceed the breaker rating.

Does this tool replace a qualified engineer?

No. It gives a fast, standards-based estimate for planning and checking. Final design must also check short-circuit withstand, earth-fault loop impedance, the exact installation method, harmonics and local regulations, and should be verified by a competent person.

📚 References

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.