Power Factor Correction Calculator 📊

Find the capacitor bank size in kVAR needed to raise your power factor from its present value to a target, with the nearest standard bank size, kVA and current before and after correction, and the reduction in cable losses.

Capacitor kVAR: Qc = kW × (tan φ1 − tan φ2)
φ1 = arccos(present PF)  ·  φ2 = arccos(target PF)

🧮 Load Data

Average or maximum demand load in kW
From the electricity bill or a power analyser (0.10 – 0.99)
0.95 is a common target; most penalties start below 0.90
Line-to-line for three phase, line-to-neutral for single phase
Results update automatically as you type.
Recommended Capacitor Bank
—kVAR
Required: — kVAR
—
kVA before
—
kVA after
—
Line current before
—
Line current after
—
Load kVAR before
—
Capacitor bank current

Power Factor Correction Formula

Capacitor required: Qc = kW × (tan φ1 − tan φ2)
φ1 = arccos(PF1)    φ2 = arccos(PF2)
kVA before = kW / PF1    kVA after = kW / PF2
Line current (3φ) = kVA × 1000 / (√3 × V)
Cable loss reduction = 1 − (PF1 / PF2)²

Capacitors supply reactive power locally, so the supply no longer has to carry it. The real power (kW) stays the same; only the kVAR drawn from the supply, and therefore the kVA and current, fall.

Worked Example: 500 kW Plant from PF 0.75 to 0.95

  1. tan φ1 = tan(arccos 0.75) = 0.882; tan φ2 = tan(arccos 0.95) = 0.329
  2. Qc = 500 × (0.882 − 0.329) = 276.6 kVAR → select a 300 kVAR bank
  3. kVA falls from 500 / 0.75 = 666.7 kVA to 500 / 0.95 = 526.3 kVA
  4. At 415 V three-phase, current falls from 927.5 A to 732.2 A, a 21.1% reduction
  5. Cable losses fall by 1 − (0.75 / 0.95)² = 37.7%

The default values in the calculator above reproduce this example.

Power Factor Correction Multiplier Table

Multiply the load in kW by the factor below to get the capacitor kVAR. Each factor is tan φ1 − tan φ2.

Present PFto 0.90to 0.95to 0.98to 1.00
0.600.8491.0051.1301.333
0.650.6850.8400.9661.169
0.700.5360.6920.8171.020
0.750.3980.5530.6790.882
0.800.2660.4210.5470.750
0.850.1350.2910.4170.620
0.90—0.1560.2810.484

Example: 200 kW from 0.80 to 0.95 → 200 × 0.421 = 84.2 kVAR, so a 100 kVAR bank.

Choosing the Target Power Factor

Fixed Bank or Automatic (APFC) Panel?

To check the present power factor from kW, voltage and current first, use the Power Factor Calculator. To size the cable feeding the capacitor bank, use the Cable Size Calculator.

FAQ

How do you calculate the kVAR needed for power factor correction?

Qc = kW × (tan φ1 − tan φ2), where φ1 = arccos of the present PF and φ2 = arccos of the target PF. Example: 500 kW from 0.75 to 0.95 needs 500 × (0.882 − 0.329) = 276.6 kVAR, so a 300 kVAR bank.

What is the power factor correction multiplier table?

It lists the factor (tan φ1 − tan φ2) for each pair of present and target power factor. Multiply the load kW by the factor to get the capacitor kVAR. From 0.75 to 0.95 the factor is 0.553.

What target power factor should I choose?

0.95 is a common target. It avoids most utility penalties without the risk of over-correction. Correcting all the way to 1.0 needs much more kVAR for little extra benefit and can push the system leading at light load.

Does power factor correction reduce my electricity bill?

It removes low power factor penalties and kVA-based demand charges where the tariff has them, and it reduces current and cable losses. It does not reduce the kWh consumed by the load itself.

What is an automatic power factor correction (APFC) panel?

An APFC panel splits the capacitor bank into several switched steps and uses a power factor controller to switch them in and out as the load changes, so the power factor stays near the target without over-correcting at light load.

When do I need detuned capacitors?

When the installation has significant non-linear load such as VFDs, UPS systems or LED drivers. Harmonics can cause resonance with plain capacitors, so a detuned bank with series reactors is used. A harmonic survey decides this.

📚 References

  • Reactive power for correction: Qc = P × (tan φ1 − tan φ2)
  • IEEE 141 (Red Book) - Electric Power Distribution for Industrial Plants
  • IEEE 1036 - Guide for the Application of Shunt Power Capacitors
  • IEC 60831 - Shunt power capacitors of the self-healing type for a.c. systems up to 1000 V
  • NEC Article 460 - Capacitors

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.