Calculate the shaft power of an air handling unit fan from its airflow and pressure, then size the motor. Enter the duty and the fan efficiency; the calculator gives air power, brake horsepower and kW at the shaft, the next standard motor after drive loss and margin, the electrical input and the specific fan power — in US or metric units.
A fan does work by moving a volume of air against a pressure. The useful air power is simply airflow × pressure; the shaft power (brake horsepower) the fan needs is larger because no fan is 100% efficient, and the motor must then cover belt losses and its own losses on top.
Use the fan total efficiency with total pressure, or the static efficiency with static pressure — mixing the two is the most common source of error. 1 in.wg = 249 Pa = 25.4 mmWG; 1 hp = 0.7457 kW.
| Fan type | Peak total efficiency | Where it is used |
|---|---|---|
| Forward-curved centrifugal | 55 – 65% | Fan coil units, small AHUs, low pressure |
| Backward-curved / backward-inclined centrifugal | 70 – 80% | AHU supply and return fans |
| Airfoil centrifugal | 80 – 86% | Large AHUs, clean air, high duty |
| Plenum (plug) fan, EC or direct drive | 65 – 75% | Modern AHUs and fan arrays |
| Vane-axial | 70 – 85% | High flow at moderate pressure, smoke extract |
| Tube-axial / propeller | 45 – 65% | Exhaust, car park and wall fans |
Peak values at the best efficiency point; a fan selected away from that point, or a small fan, is lower. Take the actual figure from the manufacturer's selection at your duty.
Specific fan power (SFP) is the electrical power per unit of airflow, in W/(L/s) or W/CFM. Energy codes use it — or an equivalent fan power limit — to cap how much a ventilation system may consume. As a guide, a good central supply and extract system lands between 1.5 and 2.5 W/(L/s) (0.7–1.2 W/CFM) for both fans together; ASHRAE 90.1 and local building regulations set the binding limits for each system type. If your result is high, reduce system pressure first: larger ducts, lower face velocity at coils and filters, and fewer fittings — see the Fan Static Pressure Calculator and the Duct Calculator.
The same check in metric: 4.719 m³/s × 623 Pa ÷ (1,000 × 0.65) = 4.52 kW at the shaft. Get the airflow from the TR to CFM Calculator, the motor current from the kW to Amps Calculator, and for AHU layouts see the AHU plant room shop drawing.
BHP = CFM × static (or total) pressure in inches of water ÷ (6,356 × fan efficiency). A fan moving 10,000 CFM against 2.5 in.wg at 65% efficiency needs 10,000 × 2.5 ÷ (6,356 × 0.65) = 6.05 bhp.
Shaft power in kW = airflow in m³/s × pressure in Pa ÷ (1,000 × fan efficiency). For 4.72 m³/s at 623 Pa and 65% efficiency: 4.72 × 623 ÷ 650 = 4.52 kW. Divide m³/h by 3,600 or L/s by 1,000 to get m³/s.
Divide the fan shaft power by the drive efficiency (about 0.95 for V-belts, 1.0 for direct drive), add a margin of 10–25%, and choose the next standard motor rating. A 6.05 bhp fan with a belt drive and 15% margin needs 7.33 hp, so a 7.5 hp (5.5 kW) motor.
Backward-curved and plenum fans used in modern air handling units reach 65–80% total efficiency at their best point, airfoil fans up to about 85%, and forward-curved fans 55–65%. Use the efficiency from the manufacturer's selection at your duty point.
SFP is the electrical power drawn by the fan motor divided by the airflow, in W per L/s (or W per CFM). It measures how efficiently a system moves air; energy codes limit it. 5.28 kW for 4,719 L/s is 1.12 W/(L/s).
By the fan laws, airflow varies with speed, pressure with speed squared and power with speed cubed. Slowing a fan to 80% of its speed cuts the airflow to 80% and the power to about 51% — the reason variable speed drives save so much energy.
Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.
Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.