AHU Fan Shaft Power Calculator: BHP, kW & Motor Size

Calculate the shaft power of an air handling unit fan from its airflow and pressure, then size the motor. Enter the duty and the fan efficiency; the calculator gives air power, brake horsepower and kW at the shaft, the next standard motor after drive loss and margin, the electrical input and the specific fan power — in US or metric units.

ASHRAE HandbookAMCA 201 / 210ASHRAE 90.1ISO 5801

Inputs

1

Fan duty

1 L/s = 3.6 m³/h = 2.119 CFM
Total (or static) pressure the fan must develop
2

Efficiencies

Forward-curved 55–65 · backward-curved / plenum 65–80 · axial 60–75
IE3 / premium: 85–95% depending on size
Reserve above the shaft power, typically 10–25%

Fan Power Formula

A fan does work by moving a volume of air against a pressure. The useful air power is simply airflow × pressure; the shaft power (brake horsepower) the fan needs is larger because no fan is 100% efficient, and the motor must then cover belt losses and its own losses on top.

US: Air hp = CFM × in.wg ÷ 6,356 → BHP = Air hp ÷ fan efficiency
Metric: Shaft power (kW) = Q (m³/s) × Δp (Pa) ÷ (1,000 × fan efficiency) · Q (m³/s) = m³/h ÷ 3,600 = L/s ÷ 1,000
Motor shaft power = BHP ÷ (1 − drive loss) → motor size = next standard rating above this, with margin
Electrical input (kW) = motor shaft power (hp) × 0.7457 ÷ motor efficiency
Specific fan power = electrical input (W) ÷ airflow (L/s)

Use the fan total efficiency with total pressure, or the static efficiency with static pressure — mixing the two is the most common source of error. 1 in.wg = 249 Pa = 25.4 mmWG; 1 hp = 0.7457 kW.

Typical Fan Efficiencies

Fan typePeak total efficiencyWhere it is used
Forward-curved centrifugal55 – 65%Fan coil units, small AHUs, low pressure
Backward-curved / backward-inclined centrifugal70 – 80%AHU supply and return fans
Airfoil centrifugal80 – 86%Large AHUs, clean air, high duty
Plenum (plug) fan, EC or direct drive65 – 75%Modern AHUs and fan arrays
Vane-axial70 – 85%High flow at moderate pressure, smoke extract
Tube-axial / propeller45 – 65%Exhaust, car park and wall fans

Peak values at the best efficiency point; a fan selected away from that point, or a small fan, is lower. Take the actual figure from the manufacturer's selection at your duty.

Choosing the Motor

  • Add the drive loss. V-belts lose around 3–7% (more on small drives); direct-drive and EC fans have none.
  • Add a margin. A reserve of 10–25% above the shaft power covers fan and installation tolerances and dirty filters. Backward-curved and airfoil fans are non-overloading — their power peaks near the design point — so they need less margin than forward-curved fans, whose power keeps rising with airflow.
  • Pick the next standard size. NEMA: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50 hp … IEC: 0.75, 1.1, 1.5, 2.2, 3, 4, 5.5, 7.5, 11, 15, 18.5, 22, 30, 37 kW …
  • Do not oversize heavily. A motor running below about 40% load loses efficiency and power factor.
  • Variable speed. With a VFD or EC motor, power follows the cube of speed: at 80% airflow the fan needs about half the power. Size the motor for the design duty, not the turned-down one.

Specific Fan Power and Energy Codes

Specific fan power (SFP) is the electrical power per unit of airflow, in W/(L/s) or W/CFM. Energy codes use it — or an equivalent fan power limit — to cap how much a ventilation system may consume. As a guide, a good central supply and extract system lands between 1.5 and 2.5 W/(L/s) (0.7–1.2 W/CFM) for both fans together; ASHRAE 90.1 and local building regulations set the binding limits for each system type. If your result is high, reduce system pressure first: larger ducts, lower face velocity at coils and filters, and fewer fittings — see the Fan Static Pressure Calculator and the Duct Calculator.

Worked Example: 10,000 CFM Supply Fan

  1. Duty: 10,000 CFM (16,990 m³/h, 4,719 L/s) at 2.5 in.wg (623 Pa), fan efficiency 65%, V-belt drive.
  2. Air power = 10,000 × 2.5 ÷ 6,356 = 3.93 hp (2.93 kW).
  3. Shaft power = 3.93 ÷ 0.65 = 6.05 bhp (4.51 kW).
  4. Belt loss 5%: motor shaft power = 6.05 ÷ 0.95 = 6.37 hp (4.75 kW).
  5. With a 15% margin: 7.33 hp → 7.5 hp motor (5.5 kW IEC frame).
  6. Electrical input at 90% motor efficiency = 6.37 × 0.7457 ÷ 0.90 = 5.28 kW.
  7. Specific fan power = 5,280 W ÷ 4,719 L/s = 1.12 W/(L/s) (0.53 W/CFM).

The same check in metric: 4.719 m³/s × 623 Pa ÷ (1,000 × 0.65) = 4.52 kW at the shaft. Get the airflow from the TR to CFM Calculator, the motor current from the kW to Amps Calculator, and for AHU layouts see the AHU plant room shop drawing.

Frequently asked questions

How do you calculate fan brake horsepower?

BHP = CFM × static (or total) pressure in inches of water ÷ (6,356 × fan efficiency). A fan moving 10,000 CFM against 2.5 in.wg at 65% efficiency needs 10,000 × 2.5 ÷ (6,356 × 0.65) = 6.05 bhp.

What is the fan power formula in kW?

Shaft power in kW = airflow in m³/s × pressure in Pa ÷ (1,000 × fan efficiency). For 4.72 m³/s at 623 Pa and 65% efficiency: 4.72 × 623 ÷ 650 = 4.52 kW. Divide m³/h by 3,600 or L/s by 1,000 to get m³/s.

How do I size the motor for an AHU fan?

Divide the fan shaft power by the drive efficiency (about 0.95 for V-belts, 1.0 for direct drive), add a margin of 10–25%, and choose the next standard motor rating. A 6.05 bhp fan with a belt drive and 15% margin needs 7.33 hp, so a 7.5 hp (5.5 kW) motor.

What is a typical AHU fan efficiency?

Backward-curved and plenum fans used in modern air handling units reach 65–80% total efficiency at their best point, airfoil fans up to about 85%, and forward-curved fans 55–65%. Use the efficiency from the manufacturer's selection at your duty point.

What is specific fan power (SFP)?

SFP is the electrical power drawn by the fan motor divided by the airflow, in W per L/s (or W per CFM). It measures how efficiently a system moves air; energy codes limit it. 5.28 kW for 4,719 L/s is 1.12 W/(L/s).

How does fan power change with speed?

By the fan laws, airflow varies with speed, pressure with speed squared and power with speed cubed. Slowing a fan to 80% of its speed cuts the airflow to 80% and the power to about 51% — the reason variable speed drives save so much energy.

References & standards

  • ASHRAE Handbook - HVAC Systems and Equipment, Fans (fan power, efficiency and fan laws)
  • AMCA Publication 201 - Fans and Systems; ANSI/AMCA Standard 210 - Laboratory Methods of Testing Fans
  • ANSI/ASHRAE/IES Standard 90.1 - fan power limitation
  • ISO 5801 - Fans: Performance testing using standardized airways

Results are preliminary engineering estimates. The edition of each standard adopted locally, the product listings and the authority having jurisdiction govern the final design.

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.