Neutral Current Calculator ⚡

Find the current in the neutral of a three-phase four-wire system from unbalanced phase currents, their power factors and the third-harmonic content of non-linear loads, and get the current to size the cable with the IEC 60364-5-52 harmonic factors.

🧮 Inputs

Phase currents (RMS)
Power factors are taken as lagging. If all three are equal, their value does not change the neutral current.
Harmonics
Auto calculate enabled (no Calculate button).
Neutral Current
—
—
From Unbalance
—
—
From 3rd Harmonic
—
—
Size Cable For
—
—

IEC 60364-5-52 Table E.52.1

3rd harmonic in phase currentSize onFactor

Neutral Current from Unbalanced Loads

In a balanced three-phase system the three phase currents cancel in the neutral. When the phases are loaded differently, the neutral carries the difference. With equal power factors on all phases:

IN = √( I1² + I2² + I3² − I1I2 − I2I3 − I3I1 )

Example: 100 A, 80 A and 60 A give IN = √(10,000 + 6,400 + 3,600 − 8,000 − 4,800 − 6,000) = √1,200 = 34.6 A. When the power factors differ, the currents are added as vectors with their own angles; the calculator does this automatically.

Why Harmonics Overload the Neutral

Non-linear loads such as LED drivers, computers and single-phase power supplies draw third-harmonic currents (150 Hz on a 50 Hz system). These "triplen" harmonics are in phase on all three lines, so instead of cancelling they add up in the neutral: with 30% third harmonic on three balanced 100 A phases, the neutral carries about 86 A even though the fundamental currents cancel completely. With heavy IT loads the neutral current can exceed the phase current.

Sizing the Cable: IEC 60364-5-52 Annex E

Third harmonic content of phase currentSelect size onReduction factor
0–15%Phase current1.0
15–33%Phase current0.86
33–45%Neutral current0.86
Above 45%Neutral current1.0

Divide the current by the factor and size a 4- or 5-core cable for the result with the Cable Size Calculator. Under the NEC, the neutral of a three-phase four-wire wye circuit serving mainly non-linear loads counts as a current-carrying conductor for ampacity adjustment (310.15(E)).

FAQ

How do you calculate neutral current in a three-phase system?

With equal power factors, IN = √(I1² + I2² + I3² − I1·I2 − I2·I3 − I3·I1). For 100 A, 80 A and 60 A this gives 34.6 A. With different power factors add the currents as vectors, and add triplen harmonic currents arithmetically.

Can the neutral current be higher than the phase current?

Yes. With non-linear loads the third-harmonic currents of the three phases add in the neutral. Above about 33% third harmonic in the phase current the neutral current exceeds the phase current, and IEC 60364-5-52 then sizes the cable on the neutral current.

Is there neutral current in a balanced load?

Not from the fundamental: balanced currents cancel. But if the loads are non-linear, their third harmonics still add up in the neutral even when the phases are perfectly balanced.

What neutral size should I use for LED lighting circuits?

LED drivers often have 25–40% third harmonic. Between 15% and 33% IEC sizes on the phase current divided by 0.86; between 33% and 45% on the neutral current divided by 0.86. Use a full-size neutral and check with the calculator.

📚 References

  • IEC 60364-5-52 Annex E: Effect of harmonic currents on balanced three-phase systems (reduction factors for triplen harmonics)
  • NFPA 70 NEC 310.15(E): neutral conductor counted as current-carrying with non-linear loads
  • IEEE 519: Recommended practice and requirements for harmonic control in electric power systems