Busbar Size Calculator: Copper & Aluminium 🟧

Size the phase, neutral and earth (PE) busbars of a switchboard from the rated current or transformer kVA, in copper or aluminium, using the current-density method.

A (mm²) = I ÷ current density  ·  1,391 A ÷ 1.6 A/mm² = 869 mm² → 100 × 10 mm copper

🧮 Inputs

Typical density for enclosed switchboards: copper 1.2–1.6 A/mm², aluminium 0.8–1.0 A/mm². Use the lower end for hot rooms (45–50 °C) and high-rated panels.
Phase busbar per phase
—

Busbar Size Calculation Method

Current: I = kVA × 1000 ÷ (√3 × V)
Required cross-section: A = I ÷ current density
Multiple bars per phase: A per bar = I ÷ (n × density × k), k = 0.90 (2 bars), 0.80 (3 bars)
PE bar (IEC 61439-1): S ≤ 16 → S · ≤ 35 → 16 · ≤ 400 → S/2 · ≤ 800 → 200 · above 800 → S/4 (mm²)

The current-density method is the standard first step in switchboard design. The final rating of a busbar system depends on the enclosure, ventilation, bar spacing, painting and ambient temperature, and must be verified by temperature-rise testing or calculation to IEC 61439, together with the short-circuit withstand of the bars and their supports.

Busbar Size Chart (Current at Typical Densities)

Flat bar (mm)Area (mm²)Cu @ 1.2 A/mm²Cu @ 1.6 A/mm²Al @ 0.8 A/mm²
12 × 336435829
15 × 345547236
20 × 360729648
25 × 3759012060
30 × 39010814472
20 × 510012016080
40 × 312014419296
25 × 5125150200100
30 × 5150180240120
50 × 3150180240120
60 × 3180216288144
40 × 5200240320160
80 × 3240288384192
50 × 5250300400200
30 × 10300360480240
60 × 5300360480240
100 × 3300360480240
120 × 3360432576288
40 × 10400480640320
80 × 5400480640320
50 × 10500600800400
100 × 5500600800400
60 × 10600720960480
120 × 5600720960480
80 × 108009601,280640
100 × 1010001,2001,600800
120 × 1012001,4401,920960

Single bar per phase. Manufacturer ratings for bare bars in free air can be higher; enclosed switchboards in hot rooms can be lower.

Worked Example: 1000 kVA Transformer Main Busbar

  1. I = 1,000,000 ÷ (1.732 × 415) = 1,391 A.
  2. Copper at 1.6 A/mm²: A = 1,391 ÷ 1.6 = 869 mm² → 100 × 10 mm (1,000 mm²) per phase.
  3. Neutral 50%: 435 mm² → 50 × 10 mm (500 mm²); use 100% for heavily non-linear loads.
  4. PE bar: S = 1,000 mm² is above 800 mm², so S/4 = 250 mm² → 50 × 5 mm.

Size the incoming cable with the Cable Size Calculator, the transformer with the Transformer Sizing Calculator, and the fault level with the Short Circuit Calculator.

FAQ

How do you calculate busbar size?

Divide the rated current by the allowed current density. For 1,250 A in copper at 1.6 A/mm², the cross-section must be at least 781 mm², so an 80 × 10 mm (800 mm²) bar per phase is used. Verify temperature rise and short-circuit strength to IEC 61439.

What current density is used for copper busbars?

Typically 1.2–1.6 A/mm² for copper in enclosed switchboards and 0.8–1.0 A/mm² for aluminium. Bare bars in well-ventilated free air can carry more; hot plant rooms call for the lower end.

How do I size the neutral busbar?

Usually 50% of the phase busbar. Use 100% (or more) where the load includes many non-linear loads such as LED drivers, IT equipment and VFDs, because third harmonic currents add up in the neutral.

How do I size the earth (PE) busbar?

IEC 61439-1 relates the PE cross-section to the phase cross-section S: equal to S up to 16 mm², 16 mm² up to 35 mm², S/2 up to 400 mm², 200 mm² up to 800 mm², and S/4 above 800 mm², unless a fault calculation gives a different size.

Why do two bars per phase not carry double the current?

The bars heat each other and the proximity effect pushes current to the outer surfaces, so two bars carry roughly 1.6–1.8 times one bar. This calculator applies a factor of 0.90 for two bars and 0.80 for three.

📚 References

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.