Motor Starter Sizing Calculator: DOL & Star-Delta ⚙️

Size the contactors, overload relay setting and cable current for a direct-on-line (DOL) or star-delta starter from the motor rating, and compare the starting current. Results update as you type.

FLC = P ÷ (√3 × V × η × PF)  ·  Star-delta: phase current = FLC ÷ √3 ≈ 0.58 × FLC, star contactor ≈ FLC ÷ 3

🧮 Motor Data

Typical 4-pole motors: efficiency 85–96% and PF 0.78–0.88, rising with size. The nameplate FLC is always best.
Full load current
—

DOL vs Star-Delta Starter

Direct-on-line (DOL)Star-delta
Starting current6–8 × FLCabout 2–2.7 × FLC (one third of DOL)
Starting torqueFull (100%)About one third
Contactors1, rated ≥ FLC (AC-3)3: main and delta ≥ 0.58 × FLC, star ≥ 0.33 × FLC
Overload relay settingFLC0.58 × FLC (relay in the phase circuit)
Motor cables1 three-core cable, ≥ FLC2 three-core cables, each ≥ 0.58 × FLC
Typical useSmall motors, most motors up to about 7.5 kWFans, pumps and compressors above about 7.5 kW that start with light load

NEC installations size the motor branch-circuit conductors at 125% of the FLC from Table 430.250 (430.22) and set overload protection from the nameplate current (430.32). Short-circuit protection (fuse or MCCB) should follow the manufacturer's Type 2 coordination tables.

Typical Motor Full Load Current Table (3-Phase)

Average catalogue values for 4-pole motors at 400 V, 50 Hz, and the same scaled to 415 V and 380 V. For guidance only; use the nameplate for selection.

kWHPFLC @ 380 V (A)FLC @ 400 V (A)FLC @ 415 V (A)DOL contactor (A, AC-3)Star-delta main/delta (A)
0.370.501.21.11.19—
0.550.741.61.51.49—
0.751.012.01.91.89—
1.11.52.72.62.59—
1.52.03.63.43.39—
2.22.95.14.84.69—
34.06.76.46.29—
45.48.88.48.19—
5.57.411.61110.6129
7.510.115.81514.5189
1114.722.12120.22518
1520.129.52827.03218
18.524.836.83533.73825
2229.543.24139.55025
3040.257.95553.06532
3749.669.56663.68040
4560.384.28077.18050
5573.7102.19793.511565
75100.5138.9132127.215080
90120.6168.4160154.218595
110147.5205.3195188.0225115
132176.9242.1230221.7265150
160214.5294.7280269.9330185
200268.1368.4350337.3400225
250335.1452.6430414.5500265

Contactor columns show the next common AC-3 rating at or above the current. Manufacturer frame sizes differ; check the catalogue.

Worked Example: 15 kW Pump Motor at 400 V

  1. FLC = 15,000 ÷ (1.732 × 400 × 0.91 × 0.84) = 28.3 A (nameplate typically about 28 A).
  2. DOL: contactor ≥ 28.3 A → 32 A (AC-3); overload set at 28.3 A; cable for at least 28.3 A; starting current about 7 × 28.3 ≈ 198 A.
  3. Star-delta: phase current 28.3 ÷ 1.732 = 16.4 A → main and delta contactors 18 A; star contactor ≥ 9.4 A → 12 A; overload set at 16.4 A; two cables of at least 16.4 A each; starting current about 66 A.

Next steps: size the cable with the Cable Size Calculator, the protective device with the Breaker Size Calculator, convert kW or HP to amps with the Load Current Calculator, and check generator starting capacity with the Generator Sizing Calculator.

FAQ

How do you size a DOL starter?

Find the motor full load current (FLC). Choose a contactor with an AC-3 rating at least equal to the FLC, set the overload relay at the FLC, and size the cable for at least the FLC (125% of FLC under NEC 430.22). Expect a starting current of about 6 to 8 times FLC.

How do you size a star-delta starter?

The main and delta contactors carry the phase current, about 0.58 × FLC, and the star contactor carries about 0.33 × FLC during starting. The overload relay, normally fitted in the phase circuit, is set at 0.58 × FLC. Two cable sets run to the motor, each carrying 0.58 × FLC.

Why does star-delta reduce starting current?

In star, each winding sees line voltage ÷ √3, so starting current and starting torque both fall to about one third of the DOL values. This suits fans and pumps that start with light load, but not loads that need high starting torque.

When should star-delta be used instead of DOL?

Typically for motors above about 7.5 kW where the supply authority or a standby generator limits starting current. The motor must be rated for delta connection at the line voltage, for example 400 V Δ / 690 V Y on a 400 V supply.

What is the full load current of a 7.5 kW motor?

About 15 A at 400 V three-phase for a typical 4-pole motor. Always use the nameplate value for final selection.

What is AC-3 rating?

AC-3 is the IEC 60947-4-1 utilisation category for squirrel-cage motors that are started and switched off while running. Contactor catalogues give the AC-3 current and kW rating at each voltage; select by AC-3, not by the thermal (AC-1) rating.