Superheat & Subcooling Calculator 🌡️

Calculate superheat and subcooling from your gauge readings for R410A, R454B, R32, R22, R134a, R407C, R404A, R290 and R1234yf. The calculator uses the correct dew and bubble temperatures for blends, gives the target superheat for fixed-orifice systems, and tells you whether the charge looks low, high or right.

🧮 Inputs

Suction line (superheat)
Liquid line (subcooling)
Leave one side blank to calculate only superheat or only subcooling.
Target superheat (fixed orifice)
Auto calculate enabled (no Calculate button).
Superheat
—
—
Subcooling
—
—
Target Superheat
—
—
Charge Check
—
—

Always follow the equipment manufacturer's charging chart where one is provided. Let the system run 15 minutes before taking readings, and check airflow and coil cleanliness before adjusting the charge.

Saturation Temperatures Used

ReadingPressureDew (vapour)Bubble (liquid)Used

Superheat and Subcooling Formulas

Superheat = suction line temperature − saturation (dew) temperature at suction pressure

Subcooling = saturation (bubble) temperature at liquid pressure − liquid line temperature

Superheat tells you how far the vapour leaving the evaporator is above its boiling point, which shows whether the evaporator is being fed the right amount of refrigerant. Subcooling tells you how far the liquid leaving the condenser is below its condensing point, which shows how much liquid is stacked in the condenser. Together they are the standard way to check the refrigerant charge of an air conditioner or heat pump.

How to Calculate Superheat, Step by Step

  1. Run the system in cooling for at least 15 minutes with clean filters and coils.
  2. Connect the low-side gauge to the suction service valve and read the suction pressure.
  3. Clamp a thermometer on the suction line about 6 in (15 cm) from the service valve, insulated from ambient air.
  4. Convert the suction pressure to the saturation temperature with the PT chart. For a blend, use the dew point.
  5. Superheat = line temperature − saturation temperature.

Example (R-410A): 118 psig suction gives a dew temperature of 39.8 °F. The suction line reads 52 °F, so superheat = 52 − 39.8 = 12.2 °F. With 63 °F indoor wet bulb and 85 °F outdoors, the target superheat for a fixed-orifice system is (3 × 63 − 80 − 85) ÷ 2 = 12 °F, so the charge is right.

How to Calculate Subcooling

Read the liquid line pressure at the liquid service valve and clamp a thermometer next to it. Convert the pressure to the bubble temperature and subtract the line temperature. Example (R-410A): 317 psig gives a bubble temperature of 99.7 °F, the line reads 90 °F, so subcooling = 99.7 − 90 = 9.7 °F.

Target Superheat Chart (Fixed Orifice)

For systems with a fixed orifice, piston or capillary tube, the correct superheat depends on the indoor heat load and the outdoor temperature. A widely used approximation of the manufacturers' charts is:

Target superheat (°F) = (3 × indoor wet bulb − 80 − outdoor dry bulb) ÷ 2
Indoor WB ↓ / Outdoor DB →65 °F70 °F75 °F80 °F85 °F90 °F95 °F100 °F105 °F110 °F115 °F
56 °F1296————————
58 °F1412107———————
60 °F1815121085—————
62 °F201816131086————
63 °F2220171412107————
64 °F24211816141186———
66 °F2624221916141296——
68 °F3027242220171412107—
70 °F323028252220181512108
72 °F3633302826232018161310
74 °F3836343128262421181614

"—" means the target is below 5 °F: do not add refrigerant under these conditions. Measure the indoor wet bulb in the return air and the outdoor dry bulb at the condenser air inlet. Where the unit has its own charging chart, use that instead.

Subcooling Calculator for TXV Systems

Systems with a TXV or electronic expansion valve are charged by subcooling, because the valve holds superheat roughly steady whatever the charge. Choose "TXV or EEV" above, enter the target subcooling from the outdoor unit's nameplate (often 8–12 °F), and the liquid line pressure and temperature. Add refrigerant if subcooling is low, recover if it is high, and allow 10–15 minutes for the system to settle after each change.

R-410A Subcooling Chart

The liquid line temperature that gives each subcooling value at common liquid line pressures:

Liquid pressureBubble temp.Line temp. for 8 °F SCfor 10 °F SCfor 12 °F SC
225 psig76.8 °F69 °F67 °F65 °F
250 psig83.6 °F76 °F74 °F72 °F
275 psig89.9 °F82 °F80 °F78 °F
300 psig95.8 °F88 °F86 °F84 °F
325 psig101.4 °F93 °F91 °F89 °F
350 psig106.7 °F99 °F97 °F95 °F
375 psig111.7 °F104 °F102 °F100 °F
400 psig116.4 °F108 °F106 °F104 °F
425 psig121.0 °F113 °F111 °F109 °F
450 psig125.3 °F117 °F115 °F113 °F

R-454B Subcooling Chart

Liquid pressureBubble temp.Line temp. for 8 °F SCfor 10 °F SCfor 12 °F SC
225 psig80.3 °F72 °F70 °F68 °F
250 psig87.2 °F79 °F77 °F75 °F
275 psig93.6 °F86 °F84 °F82 °F
300 psig99.6 °F92 °F90 °F88 °F
325 psig105.3 °F97 °F95 °F93 °F
350 psig110.6 °F103 °F101 °F99 °F
375 psig115.7 °F108 °F106 °F104 °F
400 psig120.6 °F113 °F111 °F109 °F
425 psig125.2 °F117 °F115 °F113 °F

R-454B uses the bubble temperature for subcooling. Its pressures run about 4–5% below R-410A at the same temperature, so never use an R-410A chart on an R-454B system.

Normal Superheat and Subcooling Values

SystemCharge byTypical superheatTypical subcooling
Fixed orifice / pistonSuperheatTarget from chart, about 5–20 °F (3–11 K)about 5–15 °F (3–8 K)
TXV / EEVSubcoolingabout 8–12 °F (4–7 K), held by the valveNameplate value, often 8–12 °F (4–7 K)

What Your Readings Mean

SuperheatSubcoolingMost likely cause
HighLowLow refrigerant charge (find the leak before adding)
LowHighOvercharge
HighHighRestriction in the liquid line, filter drier or metering device; TXV underfeeding
LowLowMetering device overfeeding (TXV bulb loose or stuck open) or an inefficient compressor
LowNormalLow indoor airflow: dirty filter or coil, slow blower
NormalHighOvercharge, or non-condensables; check condenser airflow and cleanliness

Dew and Bubble Temperatures for Blends (R-454B, R-407C, R-404A)

Zeotropic blends boil and condense over a temperature range called glide. At the same pressure the liquid starts to boil at the bubble temperature and the last liquid disappears at the higher dew temperature. Superheat is measured on vapour, so it uses the dew temperature; subcooling is measured on liquid, so it uses the bubble temperature. R-454B has about 2 °F of glide, R-407C about 10 °F. R-410A's glide is so small that it is treated as a single value. The full tables are in the Refrigerant PT Chart.

FAQ

How do you calculate superheat?

Measure the suction pressure and the suction line temperature. Convert the pressure to the saturation temperature with a PT chart (the dew temperature for blends) and subtract it from the line temperature. Superheat = suction line temperature − saturation temperature.

How do you calculate subcooling?

Measure the liquid line pressure and temperature at the condensing unit. Convert the pressure to the saturation temperature (the bubble temperature for blends) and subtract the liquid line temperature from it.

What should superheat be on an R-410A system?

On a TXV system superheat is usually 8 to 12 °F and the charge is set by subcooling. On a fixed-orifice system it depends on conditions: target superheat = (3 × indoor wet bulb − 80 − outdoor dry bulb) ÷ 2, typically between 5 and 20 °F.

What should subcooling be on an R-410A system?

Use the target on the outdoor unit's nameplate, usually 8 to 12 °F (4 to 7 K) for TXV systems. Charge until the measured subcooling is within about 3 °F of that target. Fixed-orifice systems typically run 5 to 15 °F but are charged by superheat.

When do you charge by superheat and when by subcooling?

Charge fixed-orifice, piston and capillary systems by superheat. Charge TXV and EEV systems by subcooling, because the valve holds superheat roughly constant whatever the charge.

What does high superheat mean?

The evaporator is starved of refrigerant. With low subcooling it usually means low charge; with high subcooling it points to a restriction in the liquid line, filter drier or metering device.

📚 References

  • Saturation properties: CoolProp (Bell et al., Ind. Eng. Chem. Res. 2014), REFPROP-equivalent equations of state
  • R-454B saturation data calibrated to Honeywell Solstice 454B published pressure-temperature chart
  • ASHRAE Handbook – Fundamentals, Thermophysical Properties of Refrigerants
  • ACCA Standard 5 / Quality Installation Specification: refrigerant charge verification by superheat and subcooling
  • Equipment manufacturers' charging charts and installation instructions (target superheat and subcooling)

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.