Heat Pump Size Calculator 🌡️

Find the right heat pump size in tons, BTU/h or kW. The calculator works out the home's design heat loss, then sizes the heat pump using how much capacity it really keeps in cold weather, and shows the balance point, any backup heat needed, and mini-split head sizes room by room.

🧮 Inputs

Heat loss
Areas in sq ft, U-values in BTU/h·ft²·°F. Use net wall area (walls minus windows and doors).
Heat loss at the design temperature below, from a room-by-room calculation.
Climate
Presets are typical 99% heating design temperatures. For a real project use the value for your town from ASHRAE climatic data or your national standard.
Heat pump
Capacity percentages are relative to the rated capacity at 47 °F (8 °C). Replace the typical values with the manufacturer's extended performance data or the NEEP listing when you have a model in mind.
Auto calculate enabled (no Calculate button).
Recommended Heat Pump Size
—
—
Design Heat Loss
—
—
Capacity at Design Temp.
—
—
Balance Point
—
—
Backup Heat
—
—

Preliminary sizing. Confirm with a room-by-room load calculation (ACCA Manual J or EN 12831) and the manufacturer's capacity tables before buying equipment.

Load vs Heat Pump Capacity

House heat lossSelected heat pumpOne size smaller

Compare Sizes

What Size Heat Pump Do I Need?

A heat pump should be sized to the heat loss of the house at the local design temperature, not to the floor area alone. Two homes of the same size can need very different heat pumps: one well insulated in a mild climate, the other older and leaky in a cold one. The second step is just as important: an air-source heat pump loses capacity as it gets colder outside, so a unit rated at 3 tons at 47 °F may deliver only 2 tons on the coldest night.

This calculator handles both steps. It works out the heat loss, then finds the smallest standard size whose cold-weather capacity meets it, or meets it down to the balance point you choose.

Heat Pump Size Chart by House Size and Climate

Heat loss and suggested size for an average insulated house with 8 ft ceilings, 70 °F indoors and a cold-climate heat pump covering the full load at the design temperature. Use it as a starting point only.

House sizeMild
32 °F (0 °C)
Cold
14 °F (−10 °C)
Very cold
3 °F (−16 °C)
Severe
−10 °F (−23 °C)
1,000 sq ft
(93 m²)
10,000 BTU/h
1 ton
14,800 BTU/h
1.5 ton
17,700 BTU/h
2 ton
21,100 BTU/h
2.5 ton
1,500 sq ft
(139 m²)
15,100 BTU/h
1.5 ton
22,200 BTU/h
2 ton
26,500 BTU/h
3 ton
31,700 BTU/h
4 ton
2,000 sq ft
(186 m²)
20,100 BTU/h
2 ton
29,600 BTU/h
3 ton
35,400 BTU/h
4 ton
42,300 BTU/h
5 ton
2,500 sq ft
(232 m²)
25,100 BTU/h
2.5 ton
37,000 BTU/h
3.5 ton
44,200 BTU/h
5 ton
52,800 BTU/h
two units
3,000 sq ft
(279 m²)
30,100 BTU/h
3 ton
44,400 BTU/h
4 ton
53,100 BTU/h
two units
63,400 BTU/h
two units

A newer, tighter house needs roughly a third less; an older, leaky one roughly half as much again. A standard heat pump in the colder columns needs either a larger size or backup heat.

How the Calculation Works

  • Quick method: heat loss = floor area × specific heat loss × (indoor − design temperature), with the specific heat loss set by the insulation level (0.5 to 3.0 W/m²K of floor area, or 0.09 to 0.53 BTU/h·ft²·°F) and adjusted for ceiling height.
  • Detailed method: Σ U × A × ΔT for walls, windows, roof and floor, plus air leakage 0.335 × ACH × volume × ΔT in watts (0.018 × ACH × cu ft × ΔT in BTU/h).
  • Heat pump capacity is modelled from its rated capacity at 47 °F (8 °C) and the percentage it keeps at 17 °F (−8 °C) and 5 °F (−15 °C), the AHRI rating points. Below its cut-out temperature an air-source unit gives nothing.
  • Size = smallest standard size whose capacity at the design temperature (or at the target balance point) meets the load.
  • Balance point = the outdoor temperature where heat pump capacity equals the house heat loss.
  • Backup heat = heat loss at design temperature − heat pump capacity at design temperature.

Typical Low-Temperature Capacity by Heat Pump Type

TypeAt 17 °F (−8 °C)At 5 °F (−15 °C)Typical cut-out
Standard air-source (single-stage)~65%~50%−4 °F (−20 °C)
Variable-speed air-source~80%~65%−13 °F (−25 °C)
Cold-climate air-source~95%~85%−22 °F (−30 °C)
Ground-source (geothermal)~100%~100%none

Percentages of rated capacity at 47 °F (8 °C). These are representative values; individual models vary widely, so use the manufacturer's extended data for the model you are considering.

Balance Point and Backup Heat

Above the balance point the heat pump has more capacity than the house needs and cycles or modulates down. Below it, something else has to make up the difference: electric resistance strips, a furnace in a dual-fuel system, or a larger heat pump. Sizing to cover the full load at the design temperature gives a balance point at or below it and needs no backup. Sizing to a balance point of around 25–30 °F (−4 to −1 °C) keeps the heat pump smaller and closer to the cooling load, with backup heat for the few coldest hours of the year.

Heating Size vs Cooling Size

In cold climates the heating load is usually much bigger than the cooling load. A heat pump sized for heating can then be oversized for cooling, which in humid regions means short cycles and poor dehumidification. A variable-speed or cold-climate unit that can turn down handles this well; with a single-stage unit it is often better to size closer to the cooling load and add backup heat. Enter your cooling load to get this check, or estimate it with the BTU AC Sizing Calculator.

Sizing a Mini-Split Heat Pump Room by Room

With ductless mini-splits each indoor head serves one room, so each needs its own size. Tick "Size mini-split heads room by room", list the rooms and their floor areas, and the tool splits the heat loss across them and picks a standard head size for each (6,000 to 36,000 BTU/h, or 2.0 to 10 kW). Avoid oversizing small bedrooms: the smallest heads already cover most of them.

Worked Example

The default case: a 2,000 sq ft house with 8 ft ceilings and average insulation, 70 °F indoors, in a very cold climate with a 3 °F design temperature.

  • Heat loss = 2,000 sq ft × 0.264 BTU/h·ft²·°F × (70 − 3) °F = 35,400 BTU/h (10.4 kW), or 17.7 BTU/h per sq ft
  • A cold-climate heat pump keeps about 83% of its rated capacity at 3 °F, so it needs 35,400 ÷ 0.83 = 42,500 BTU/h of rated capacity
  • Next standard size: 4 tons (48,000 BTU/h), giving about 40,000 BTU/h at 3 °F, so no backup heat is needed
  • A 3.5 ton unit would give 35,000 BTU/h at 3 °F, 99% of the load. Many designers would accept it and let the house drift a degree on the coldest night; the comparison table shows both
  • A standard single-stage heat pump keeps only about 48% at 3 °F. Covering the full load would take over 6 tons, so instead size it to a 25 °F balance point: 3 tons, balance point 22 °F, and about 5.4 kW of backup heat (a 6 kW strip) at the design temperature

Related Tools

For a detailed room heat balance use the Room Heat Load Calculator, for running cost the AC Running Cost Calculator, and for unit conversions the TR to kW converter. Wall, roof and window U-values come from the construction details or the energy code.

FAQ

What size heat pump do I need for a 2,000 sq ft house?

It depends on insulation and climate more than area. An average insulated 2,000 sq ft house loses about 20,000 BTU/h at 32 °F and about 35,000 BTU/h at 3 °F. With a cold-climate heat pump that is roughly a 2 ton unit in a mild climate and 3.5 to 4 tons in a very cold one.

How many BTU per square foot does a heat pump need?

For heating, a typical insulated house needs about 10 to 25 BTU/h per square foot at the design temperature, more for older houses and cold climates, less for new tight ones. Older rules of thumb of 40 to 60 BTU per square foot usually oversize the equipment.

What is a heat pump balance point?

The outdoor temperature at which the heat pump's capacity exactly equals the house heat loss. Below it the heat pump cannot keep up on its own and backup heat makes up the difference.

Should a heat pump be sized for heating or cooling?

In hot climates size for cooling. In cold climates the heating load is larger: either size for heating with a variable-speed or cold-climate unit that can turn down for cooling, or size closer to the cooling load and add backup heat below the balance point.

Can a heat pump be too big?

Yes. An oversized heat pump short-cycles, wears faster, removes less humidity in summer and costs more to buy. Size it to the calculated load at the design temperature rather than adding large safety margins.

📚 References

  • ACCA Manual J (residential load calculation) and Manual S (equipment selection)
  • ASHRAE Handbook – Fundamentals: climatic design conditions (99% heating dry-bulb) and heat loss calculation
  • EN 12831-1: Energy performance of buildings – Method for calculation of the design heat load
  • AHRI Standard 210/240: heat pump rating conditions at 47 °F, 17 °F and 5 °F
  • NEEP Cold Climate Air Source Heat Pump Specification and product list (capacity at 5 °F)