ESE Lightning Arrester Protection Radius Calculator ⚡

Calculate the protection radius (Rp) of an ESE lightning arrester with the NF C 17-102 formula. Enter the protection level, the arrester's ΔT and the mast height, then check whether a roof is covered, the height a single arrester would need, and how many arresters a larger roof needs.

🧮 Inputs

ΔT comes from the arrester's test certificate (typically 15 to 60 µs). NF C 17-102:2011 limits the value used in the calculation to 60 µs.
Roof to protect (optional)
The coverage check assumes one arrester in the centre of a rectangular roof, or a regular grid of arresters on larger roofs.
Auto calculate enabled (no Calculate button).
Protection Radius Rp
—
—
Single Arrester
—
—
Height Needed
—
—
Arresters for Roof
—
—

ESE systems follow NF C 17-102 and similar national standards; they are not covered by IEC 62305 or NFPA 780. Check that the authority having jurisdiction accepts ESE before designing with it.

Plan View

Rp at Other Heights

Height hLevel ILevel IILevel IIILevel IV

ESE Protection Radius Formula (NF C 17-102)

Rp(h) = √( 2·r·h − h² + ΔL·(2·r + ΔL) )  for h ≥ 5 m

Rp(h) = h × Rp(5) ÷ 5  for 2 m ≤ h < 5 m

Example: Level I, ΔT = 60 µs, h = 5 m: Rp = √(2 × 20 × 5 − 25 + 60 × (40 + 60)) = √6175 = 78.6 m. Raising the mast above 5 m adds very little: at h = 10 m Rp is 79.4 m. The ESE efficiency and the protection level matter far more than extra height.

ESE Protection Radius Table

Rp in metres for common ΔT values:

ΔTLevelh = 2 mh = 3 mh = 4 mh = 5 mh = 6 mh = 8 mh = 10 mh = 15 mh = 20 m
25 µsLevel I172534424343444545
25 µsLevel II202939494950515354
25 µsLevel III233446575859616365
25 µsLevel IV263952656667697275
45 µsLevel I253851636364646565
45 µsLevel II284257717172727374
45 µsLevel III324864818182838586
45 µsLevel IV365472899091929597
60 µsLevel I314763797979798080
60 µsLevel II355269868787888989
60 µsLevel III39587897979899101102
60 µsLevel IV436485107107108109111113

Choosing the Protection Level

The protection level comes from a lightning risk assessment, to IEC 62305-2 or the method in NF C 17-102 Annex A. It depends on the lightning density at the site, the building size and use, its contents and the consequences of damage. Level I is the most stringent (hospitals, fuel and explosive stores, critical facilities); Level IV the least.

Installation Points

Size the earth electrodes with the Earthing Calculator. Download typical installation details from our AutoCAD electrical installation details.

FAQ

How do you calculate the protection radius of an ESE lightning arrester?

Use the NF C 17-102 formula Rp = √(2rh − h² + ΔL(2r + ΔL)) for heights of 5 m or more, where r is 20, 30, 45 or 60 m for protection levels I to IV, h is the tip height above the protected surface and ΔL in metres equals the ESE efficiency ΔT in microseconds. Below 5 m, Rp = h × Rp(5) ÷ 5.

What is ΔT in an ESE lightning arrester?

ΔT is how much earlier, in microseconds, the ESE terminal launches its upward leader compared with a simple rod under the same conditions. It is measured in a high-voltage laboratory and stated on the test certificate. NF C 17-102 caps the value used for design at 60 µs.

What is the protection radius of a 60 µs ESE at 5 m?

About 79 m for Level I, 87 m for Level II, 97 m for Level III and 107 m for Level IV.

Does increasing the mast height increase ESE coverage?

Up to 5 m it does strongly, because below 5 m the radius grows in proportion to height. Above 5 m the gain is small: for Level I and 60 µs the radius only grows from 79 m at 5 m to 80 m at 20 m.

Is ESE accepted by IEC 62305 and NFPA 780?

No. ESE terminals are designed to NF C 17-102, UNE 21186 and similar national standards, and are widely used in Europe, the Middle East and Asia, but IEC 62305 and NFPA 780 do not recognise an enlarged protection radius. Always confirm that the local authority accepts ESE.

📚 References

  • NF C 17-102:2011 – Protection against lightning – Early streamer emission lightning protection systems
  • UNE 21186:2011 – Lightning protection: early streamer emission lightning conductors
  • IEC 62305-2 – Protection against lightning: Risk management (selection of the protection level)