Sprinkler Spacing Calculator (NFPA 13) 💦

Lay out standard spray upright or pendent sprinklers in a rectangular room: the number of sprinklers, spacing in each direction, area per sprinkler and distance from walls, checked against NFPA 13. Optionally get the flow and pressure at each sprinkler.

S ≤ Smax in both directions  ·  As = S × L ≤ Amax  ·  wall distance ≤ Smax ÷ 2

🧮 Room & Hazard

Rectangular rooms with smooth ceilings. Obstructions, beams, sloped ceilings, extended coverage and storage sprinklers have extra rules in NFPA 13.
Sprinklers required
—

NFPA 13 Sprinkler Spacing and Coverage Table

Standard spray upright and pendent sprinklers. Values are the maximum protection area per sprinkler and maximum distance between sprinklers.

Hazard / systemMax area (ft²)Max area (m²)Max spacing (ft)Max spacing (m)Max to wall
Light hazard, hydraulically calculated (noncombustible or unobstructed construction)22520.9154.67.5 ft (2.29 m)
Light hazard, pipe schedule system20018.6154.67.5 ft (2.29 m)
Light hazard, combustible obstructed construction16815.6154.67.5 ft (2.29 m)
Ordinary hazard (Group 1 and 2)13012.1154.67.5 ft (2.29 m)
Extra hazard, hydraulically calculated (density ≥ 0.25 gpm/ft²)1009.3123.76 ft (1.83 m)
Extra hazard, pipe schedule or density < 0.25 gpm/ft²908.4123.76 ft (1.83 m)
High-piled storage (density ≥ 0.25 gpm/ft²)1009.3123.76 ft (1.83 m)

All hazards: minimum 6 ft (1.8 m) between sprinklers and at least 4 in (102 mm) from walls. Check the edition of NFPA 13 adopted locally and the sprinkler's listing.

Worked Example: Ordinary Hazard Room 20 × 12 m

  1. Limits: 4.6 m maximum spacing and 12.1 m² per sprinkler.
  2. Along 20 m: 20 ÷ 4.6 = 4.3 → 5 rows at 4.0 m. Along 12 m: 12 ÷ 4.6 = 2.6 → 3 rows at 4.0 m gives 16 m² per sprinkler, too much.
  3. 4 rows at 3.0 m gives 4.0 × 3.0 = 12.0 m² ≤ 12.1 m² ✓, so the layout is 5 × 4 = 20 sprinklers, 2.0 m and 1.5 m from the walls.
  4. At 8.1 mm/min (0.20 gpm/ft²) over 12.0 m², each sprinkler needs about 97 L/min (25.7 gpm); a K 5.6 sprinkler needs about 21 psi (1.45 bar) at the most remote head.

Continue with the Sprinkler K-Factor Calculator, Sprinkler Density Calculator and Fire Hydraulic Calculator, then size the supply with Fire Pump Sizing and Fire Water Tank Sizing.

FAQ

What is the maximum sprinkler spacing under NFPA 13?

For standard spray upright and pendent sprinklers, 15 ft (4.6 m) for light and ordinary hazard and 12 ft (3.7 m) for extra hazard and high-piled storage, with the area per sprinkler also limited by hazard.

What is the maximum area per sprinkler?

225 ft² (20.9 m²) for hydraulically calculated light hazard, 130 ft² (12.1 m²) for ordinary hazard and 100 ft² (9.3 m²) for hydraulically calculated extra hazard. Pipe schedule systems and some construction types have smaller limits.

How far can a sprinkler be from a wall?

No more than half the allowable spacing, for example 7.5 ft (2.3 m) where the spacing limit is 15 ft, and not less than 4 in (102 mm) from the wall.

What is the minimum distance between sprinklers?

6 ft (1.8 m) for standard spray sprinklers, to prevent one sprinkler wetting its neighbour and delaying its operation, unless baffles are installed.

How do you calculate the number of sprinklers in a room?

Divide the room length and width by the maximum spacing and round up to get rows and columns, then check that the actual spacing in each direction multiplied together does not exceed the maximum area per sprinkler. Increase the rows if it does.

Does this calculator replace a hydraulic calculation?

No. It sets the layout. The hydraulic calculation then checks that the water supply delivers the design density over the design area, starting from the most remote sprinkler.